8  Reactive Power Control

Operating Manual

SCCP-US-BE-US_en-52

61

8.1.10 VArCtlVol Procedure

The reactive power is controlled depending on the line voltage. The reactive power setpoint is adjusted in stages.

Figure 24: Characteristic curve for reducing reactive power depending on line voltage

If the line voltage changes by the configurable voltage difference Q-VDif for the configurable duration of Q-VDifTm,

the reactive power target value is adjusted to the value Q-VArGr.
The parameterization of this function is based on the medium voltage.

8.1.11 VArCtlVolHystDb Procedure

By supplying reactive power, the inverter helps perform voltage-stabilizing measures in the event of overvoltage or

undervoltage. The parameterization is performed using a reactive power/voltage characteristic curve.

The characteristic curve can be configured flexibly by parameterizing the slope, a sort of "deadband" through two

voltage points and a hysteresis.

Contact the SMA Service Line before changing any parameters.
The VArCtlVol procedure may only be selected and configured after consultation with the SMA Service Line.

Parameters used

Q-VDif
Q-VArGra
Q-VDifTm
Q-VRtgOfsNom

Contact the SMA Service Line before changing any parameters.
The VArCtlVolHystDb procedure may only be selected and configured after consultation with the

SMA Service Line.