3  Product Description

SMA America, LLC

38

SCCP-US-BE-US_en-52

Operating Manual

With limited dynamic grid support, the inverter interrupts the grid feed-in during the grid voltage drop.

Figure 15: Maximum duration of a voltage dip that the inverter can work through without disconnecting from the utility grid

The operating mode of the dynamic grid support is set via the parameter FRTMod. With this, the full dynamic grid support

(FRT_BDEW), the full dynamic grid support with FRT characteristic curve (FRT_SDLWindV) and the limited dynamic grid

support (FRT_Partial) can be selected.
The level of reactive current provided during full dynamic grid support is determined via the parameter FRTArGraNom.

The level of reactive current provided during full dynamic grid support with FRT characteristic curve is determined via the

parameters FRT2ArGraNomHi and FRT2ArGraNomLo.

Ratio V

Grid

/V

Behavior of the inverter

90% to 100%

The ratio of line voltage V

Grid

to nominal voltage V is in the normal range and the inverter feeds in

without any problem.

20% to 90%

The ratio of line voltage V

Grid

to nominal voltage V is in the critical range. There is a disturbance

in the utility grid.
While this disturbance remains present, the inverter supports the electricity grid with reactive

current.
The inverter can bridge disturbances of up to two seconds without disconnecting from the utility

grid.
If the set grid monitoring time is exceeded during this period, the inverter disconnects from the utility

grid.

0% to 20%

The ratio of line voltage V

Grid

to nominal voltage V is in the critical range. There is a disturbance

in the utility grid.
While this disturbance remains present, the inverter supports the electricity grid with reactive

current.
The inverter can bridge disturbances of up to one second without disconnecting from the utility grid.

The requirement is that the relationship V

Grid

/V was >= 90% before the error occurred.

If the set grid monitoring time is exceeded during this period, the inverter disconnects from the utility

grid.