8  Reactive Power Control

SMA America, LLC

58

SCCP-US-BE-US_en-52

Operating Manual

The analog value is converted into a reactive power setpoint. The electrical current strength of the connected signal

determines the setpoint.
The analog measured values must be between 4 mA and 19 mA. If the analog signal is less than 2 mA, the error

message will be displayed in the Q-VArModFailStt instantaneous value.

The analog value is converted to a setpoint for power limitation. Here, the parameter Pmax is the end point of the linear

characteristic curve.

Figure 22: Limiting the parameter Pmax to the parameter Qmax

If the value of Pmax exceeds the value of Qmax, the characteristic curve of the value Q

max

will be limited to Qmax

and the reactive power value in the range from +Q

max

to +P

max

will remain constant at Qmax.

If the value of ‒Pmax falls below the value of ‒Qmax, the characteristic curve of the value ‒Q

max

will be limited to

Qmax and the reactive power value in the range from ‒Q

max

to

‒P

max

will remain constant at ‒Qmax.

Signal

Power limit

Description

< 2 mA

Last valid value or 0 kVAr

after restart

Signal is in the invalid range.

2 mA to 4 mA

− Pmax

The maximum amount of negatively excited reactive power is fed in.

4 mA

− Pmax

Starting point of the characteristic curve

Maximum amount of negatively excited reactive power is fed in.

11.5 mA

0 kVAr

Zero-crossing of the characteristic curve

No reactive power is fed in.

> 19 mA

+Pmax

End point of the characteristic curve

Maximum amount of positively excited reactive power is fed in.