3.2.4 Touch Display

Different kinds of inverter data can be viewed on the touch display. Settings such as language, time and brightness can

be set, but inverter parameters cannot be set from the touch display.
The display area is activated by touching the touch display. Tapping the symbols on the touch display activates the

corresponding functions. If the touch display is not touched for five minutes, it will shut off.

Grid monitoring

The inverter is in the "Grid monitoring" operating state. Waiting for valid AC grid

appears in the touch display.
The grid limits will be monitored continuously from now on. If a grid fault does not occur

during the grid monitoring time, the AC contactor closes and the inverter switches to the

"Grid monitoring time reached" operating state.
If the grid limits are exceeded during the monitoring time, the inverter will restart "Grid

monitoring".
With the option "Q at Night", the inverter switches to the "Q at Night" operating state if the

time specified in the parameter PvStrT has elapsed and the start voltage PvVtgStrLevMin

has not been reached (see Section 8.3 "Q at Night", page 65).

Grid monitoring time

reached

The inverter is in the "Grid monitoring time reached" operating state. Waiting for PV

voltage or Waiting for electric utility company appears on the touch display.
If the input voltage V

PV

exceeds the start voltage PvVtgStrLevMin, the inverter waits until

the time specified in the PvStrT parameter elapses. If the input voltage V

PV

does not fall

below the start voltage PvVtgStrLevMin during this time, the inverter checks whether the

utility grid is available. If a valid utility grid is available, the inverter switches to the operating

state "Startup".
The start voltage PvVtgStrLevMin must be adjusted to conform with the PV array

connected to the inverter.

Startup

The inverter is in the "Startup" operating state. Operation appears in the touch display.
The inverter moves to its initial operating point and begins the grid feed-in process.

MPP load operation

In the MPP operating state, the inverter feeds power into the utility grid and operates

permanently at the maximum power point (MPP). Operation and the rate of power feed-in

are shown in the touch display.
If the measured power P

PV

during the time interval PvPwrMinT is less than the minimum

feed-in voltage PvPwrMin or the key switch is set to Stop, the inverter switches to the

"Shutdown" operating state.
With the order option "Q at Night", the inverter switches to the operating state "Q at Night"

if the measured power P

PV

during the time interval PvPwrMinT is less than the minimum

feed-in power PvPwrMin (see Section 8.3 "Q at Night", page 65).

Shutdown

The inverter is in the "Shutdown" operating state. Operation appears in the touch display.
If the key switch is set to Stop, the inverter switches to the "Stop" operating state.

The AC contactor and the DC switching device open automatically.
If the inverter shuts down because the feed-in conditions are no longer met,

the inverter switches to the "Grid monitoring" operating state.

Fault

If a disturbance occurs during operation, the inverter switches off and displays Fault and

the disturbance in the touch display (see Section 11 "Troubleshooting", page 77).

Designation

Description