8  Reactive Power Control

SMA America, LLC

70

SCCP-US-BE-US_en-52

Operating Manual

Figure 33: Characteristic curve for reducing reactive power with hysteresis

Figure 34: Characteristic curve for reducing reactive power with deadband and hysteresis

The parameter Q-VArTmsSpnt determines the delay time which must elapse before the calculated reactive power

setpoint is actively used.