SMA SC 500CP-US-10 600V User Manual

Page 85

background image

SMA America, LLC

11  Troubleshooting

Operating Manual

SCCP-US-BE-US_en-52

85

7704

Contactor error at the DC disconnection

point.

30 s

A

• When disconnecting the

inverter from voltage sources,

check that all motor-driven

circuit breaker switches are set

to the OFF position. If the

switches are not all set to the

OFF position, set all the

switches to the OFF position

(see the Sunny Central

installation manual).

• Contact the SMA Service Line.

7706

Error at the digital input of the AC

disconnection point

30 s

A

• Contact the SMA Service Line.

7707

Contactor error at the AC disconnection

point

30 s

A

7708

No Advanced Remote GFDI response.

7709

90% of the switch cycles of the integrated

DC Switch reached.

30 s

30 s

7710

100% of the switch cycles of the integrated

DC Switch reached.

30 s

30 s

7714

Maximum GFDI switch cycles reached.

30 s

30 s

7801

Surge arrester is faulty.

• Check the surge arrester.

7901

An inverse current has occurred at the PV

array.

1 min

D

x

• Contact the SMA Service Line.

8701

External active power setpoints are less

than 2 mA and therefore invalid.
The last valid value is used or Pmax is

used after the day has changed.
Once the valid setpoints are available

again, they are used.

8702

There are several digital power setpoints

present.

8703

External displacement power factor cos φ

is invalid.

8704

External active and reactive power

setpoints are invalid.

9000

Power electronics self-test is being carried

out. This message disappears once the

self-test has been run.

W

W

9008

Doors were opened during operation.

30 s

1 min

9009

The fast stop was tripped manually.

30 s

30 s

• Switch the fast stop on again

after correcting the error.

Error no.

Explanation

Behavior of the

inverter

Corrective measures

S 1

S 2