11  Troubleshooting

SMA America, LLC

82

SCCP-US-BE-US_en-52

Operating Manual

3601

Leakage current to ground has occurred in

the PV array or the threshold defined in

parameter RisoCtlWarn has been

reached.

W

W

• Check the grounding and

equipotential bonding.

• Check the module wiring and

PV system design.

• Check the RisoCtlWarn

parameter.

3803

The DC current of the PV array is too high. 1 min

D

x

• Check the DC input current.
• Check the module wiring and

plant design.

4003

Reverse currents detected in the PV array

or DC connection polarity is reversed.

30 s

A

• Check PV modules for short

circuits.

• Check the module wiring and

plant design.

• Make sure the DC terminals

have the correct polarity.

Error no.

Explanation

Behavior of the

inverter

Corrective measures

S 1

S 2

R