Page 39

background image

SMA America, LLC

3  Product Description

Operating Manual

SCCP-US-BE-US_en-52

39

Contact the SMA Service Line to activate the function "FRT" and to change the operating mode. Contact the SMA Service

Line before setting the FRTArGraNom parameter to a value greater than 2.

3.7.5 Decoupling Protection Ramp

After a grid error, the inverter restarts at a maximum of 10% of nominal power per minute using a decoupling protection

ramp. You have the option of switching this decoupling protection ramp on or off. If you deactivate the decoupling

protection ramp, the inverter runs up to the maximum power in the shortest time possible. If you wish to deactivate the

decoupling protection ramp, contact the SMA Service Line.

3.7.6 Grid Management Shutdown

If the utility grid becomes unstable and overloaded, the grid management service requires that the inverter disconnects

from the grid immediately. In such cases, the relevant signal will be sent by the grid operator or the safety system at the

grid transfer point. The inverter disconnects from the utility grid immediately and displays the error message 9013. The

error will be reset in the inverter after a corresponding signal is sent by the grid operator or the transfer point's safety

system.

Full and limited dynamic grid support and islanding detection
The function "FRT" cannot be active at the same time as the function "Active Islanding Detection". If the "FRT" function

is activated , the "Active Island Detection" function is deactivated automatically. Changing this parameter therefore

results in the loss of the UL listing.
The "FRT" function can be active at the same time as the "External Islanding Detection" function. For this, the

parameters VCtllLimTm and VCtlllLimTm must be set to 2,000 ms.