11  Troubleshooting

SMA America, LLC

78

SCCP-US-BE-US_en-52

Operating Manual

11.3 Acknowledging Error Messages

Once the disturbance is rectified, you can acknowledge the error using the key switch on the inverter or the user interface.

11.3.1 Acknowledging the Error Messages via the Key Switch

Procedure:

1. If there is an insulation error, switch the insulation monitoring device back on.
2. Turn the key switch to Stop and then back to Start after two seconds.

11.3.2 Acknowledging Errors via the User Interface

You can only acknowledge error messages via the user interface after the installer password has been entered.

Procedure:

1. If an insulation error has occurred, switch the insulation monitoring device back on.
2. Log in to the user interface.
3. Select the parameter Ackn in the device that displays the error and set it to Ackn.
4. Confirm entry with [Save].

11.4 Error Messages

11.4.1 Behavior of the Inverter under Fault Conditions

If a disturbance occurs during inverter operation, this may be due to a warning or error.
Each disturbance has two error levels that influence the display and system behavior. Only a few disturbance types cause

the inverter to behave differently in the two error levels. The error level changes from 1 to 2 if the disturbance occurs five

times within two hours or occurs permanently for two hours.
A warning does not affect the behavior of the inverter. The cause of the warning must be established and remedied.
If operation is interrupted due to an error, the inverter switches to the "Fault" operating state and opens the

AC contactor and the DC switching device. The error, error number, error message and a symbol are displayed on the

touch display (see Section 11.2.1 "Reading Error Messages via Touch Display", page 77).
If the cause of the error is rectified and the error is no longer displayed, the error is deleted from the fault memory.

To view previous errors after they have been deleted from the fault memory, an event file is saved on the SD card.

The time when an error occurred and the type of error are entered in the event file.
You will find the following information in the error tables in Section 11.4.2, 11.4.3 and 11.4.4:

Dealing with disturbances
Error messages should only be acknowledged once the underlying causes have been eliminated.
If the causes of the disturbance have not been eliminated, the disturbance will still be detected after

acknowledgement and the error message will appear again.

Dealing with disturbances
Error messages should only be acknowledged once the underlying causes have been eliminated.
If the causes of the disturbance have not been eliminated, the disturbance will still be detected after

acknowledgement and the error message will appear again.

Information

Level

Behavior

Explanation

Error no.

Clearly identifies the disturbance present

Explanation

Identifies possible causes of the disturbance present