13  Parameters

SMA America, LLC

106

SCCP-US-BE-US_en-52

Operating Manual

13.1.5 Device-Internal Values

* These parameters can only be viewed and changed after the installer password has been entered.

Name

Description

Value/range

Explanation

Default

value

PvPwrMinTr

Threshold for starting the

MPP tracker

0 W to 20 kW

20 kW

PvPwrMinTrT

Timeout for starting the

MPP tracker

1 s to 1,800 s

600 s

PvVtgStrLevMin*

Threshold for switching to

feed-in operation

0 V to 1,800 V

SC 500CP-US-10

500 V

SC 630CP-US-10 600V

390 V

SC 630CP-US-10

610 V

SC 720CP-US-10

675 V

SC 750CP-US-10

715 V

SC 800CP-US-10

760 V

SC 850CP-US-10

760 V

SC 900CP-US-10

770 V

PVStrT

Timer: Target status switches

from Wait-PV to Grid-Connect

when timer elapses

1 s to 300 s

90 s

VArGra**

Gradient of reactive power

change (VAr/s)

0%/s to 200%/s

20%/s

QoDInvCurPv**

Maximum allowed reverse

current to the PV array

− 1,600 A to 0 A

− 60 A

RmpVtgPvSNg

Internal channel: negative

PV voltage ramp (DSP)

0 V/s to 200 V/s

200 V/s

RmpVtgPvSPos

Internal channel: positive

PV voltage ramp (DSP)

0 V/s to 200 V/s

200 V/s

MppFact

Ratio between maximum power

P

MPP

of the PV cell at the

maximum power point and the

product of open-circuit voltage

V

OC

and short-circuit current I

SC

0.5 to 1

0.8

Serial Number *

Serial number of the inverter

0 to 2,147,483,647 ‒

CntrySet*

Setting the Country

Country-specific

CardFunc*

MMC/SD card function

ForcedWrite

SD card logout

StoFailHis

Writes error history to

SD card

DtSet

Date

20060101 to

20991231

0

TmSet

Time

0 to 235959

0