beautypg.com

SMA SC 500CP-US-10 600V User Manual

Page 96

background image

13  Parameters

SMA America, LLC

96

SCCP-US-BE-US_en-52

Operating Manual

PF-WLockInVtg**

Power at which the cos

φ(P) characteristic curve

is activated, in % relative

to the nominal voltage

0% to 110%

0%

PF-WLockOutVtg** Power at which the cos

φ(P) characteristic curve

is deactivated, in %

relative to the nominal

voltage

0% to 110%

0%

PF-WLockTm**

Waiting time for

activating or deactivating

the cos φ(P) characteristic

curve

0 s to 100 s

2 s

Q-VDif**

Definition or the voltage

change that leads to a

reactive power change.

0.1% to 10%

The value corresponds to

the nominal voltage VRtg.

1%

Q-VArGra**

Definition of the reactive

power setpoint change

during a voltage step.

0% to 100%

The value corresponds to

the nominal power Pmax.

1%

Q-VDifTm**

Time span in which a

voltage change must be

present before the

reactive power target

value Q-VArGra

changes.

0 s to 120 s

1 s

Q-VRtgOfsNom**

Changes the nominal

voltage VRtg of the

voltage-dependent

reactive power control
The parameter is active

only if parameter

Q-VArMod is set to

VArCtlCol.

− 10% to +10%

0%

Q-VArGraNom**

Reactive power gradient

0%/V to 40.06%/V

SC 500CP-US-10

0%/V

0%/V to 54.15%/V

SC 500CP-US-10 600V

0%/V to 31.47%/V

SC 630CP-US-10

0%/V to 27.82%/V

SC 720CP-US-10

0%/V to 26.70%/V

SC 750CP-US-10

0%/V to 25.04%/V

SC 800CP-US-10

0%/V to 23.56%/V

SC 850CP-US-10

0%/V to 22.25%/V

SC 900CP-US-10

Q-VolWidNom**

Voltage range

0% to 20%

0%

Q-VolNomP1**

Voltage at point 1

80% to 120%

100%

Name

Description

Value/range

Explanation

Default

value