13 Parameters
SMA America, LLC
96
SCCP-US-BE-US_en-52
Operating Manual
Power at which the cos
φ(P) characteristic curve
is activated, in % relative
to the nominal voltage
0% to 110%
‒
0%
PF-WLockOutVtg** Power at which the cos
φ(P) characteristic curve
is deactivated, in %
relative to the nominal
voltage
0% to 110%
‒
0%
PF-WLockTm**
Waiting time for
activating or deactivating
the cos φ(P) characteristic
curve
0 s to 100 s
‒
2 s
Q-VDif**
Definition or the voltage
change that leads to a
reactive power change.
0.1% to 10%
The value corresponds to
the nominal voltage VRtg.
1%
Definition of the reactive
power setpoint change
during a voltage step.
0% to 100%
The value corresponds to
the nominal power Pmax.
1%
Time span in which a
voltage change must be
present before the
reactive power target
value Q-VArGra
changes.
0 s to 120 s
‒
1 s
Q-VRtgOfsNom**
Changes the nominal
voltage VRtg of the
voltage-dependent
reactive power control
The parameter is active
only if parameter
Q-VArMod is set to
VArCtlCol.
− 10% to +10%
‒
0%
Reactive power gradient
0%/V to 40.06%/V
SC 500CP-US-10
0%/V
0%/V to 54.15%/V
SC 500CP-US-10 600V
0%/V to 31.47%/V
SC 630CP-US-10
0%/V to 27.82%/V
SC 720CP-US-10
0%/V to 26.70%/V
SC 750CP-US-10
0%/V to 25.04%/V
SC 800CP-US-10
0%/V to 23.56%/V
SC 850CP-US-10
0%/V to 22.25%/V
SC 900CP-US-10
Voltage range
0% to 20%
‒
0%
Q-VolNomP1**
Voltage at point 1
80% to 120%
‒
100%
Name
Description
Value/range
Explanation
Default
value