13  Parameters

Operating Manual

SCCP-US-BE-US_en-52

95

QoDQ-VArNom

Reactive power in % in

the operating state "Q at

Night"

− 100% to 100%

0

PF-PF

Displacement power

factor cos φ
The lower limit is defined

by parameter

PFAbsMin.

0.5 to 1

1

PF-PFExt

Excitation of the

displacement power

factor cos φ.

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-PFStr**

Displacement power

factor cos φ at

characteristic curve

point 1
The lower limit is defined

by parameter

PFAbsMin.

0.5 to 1

0.8

PF-PFExtStr**

Excitation of the

displacement power

factor cos φ at

characteristic curve

point 1

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-PFStop**

Displacement power

factor cos φ at

characteristic curve

point 2
The lower limit is defined

by parameter

PFAbsMin.

0.5 to 1

0.8

PF-PFExtStop**

Excitation of the

displacement power

factor cos φ at

characteristic curve

point 2

OvExt

Overexcited

OvExt

UnExt

Underexcited

PF-WStr**

Specifies the feed-in

capacity in % at

characteristic curve

point 1

0% to 90%

0%

PF-WStop**

Specifies the feed-in

capacity in % at

characteristic curve

point 2

10% to 100%

100%

Name

Description

Value/range

Explanation

Default

value