13 Parameters
Operating Manual
SCCP-US-BE-US_en-52
95
QoDQ-VArNom
Reactive power in % in
the operating state "Q at
Night"
− 100% to 100%
‒
0
PF-PF
Displacement power
factor cos φ
The lower limit is defined
by parameter
PFAbsMin.
0.5 to 1
‒
1
PF-PFExt
Excitation of the
displacement power
factor cos φ.
OvExt
Overexcited
OvExt
UnExt
Underexcited
Displacement power
factor cos φ at
characteristic curve
point 1
The lower limit is defined
by parameter
PFAbsMin.
0.5 to 1
‒
0.8
Excitation of the
displacement power
factor cos φ at
characteristic curve
point 1
OvExt
Overexcited
OvExt
UnExt
Underexcited
PF-PFStop**
Displacement power
factor cos φ at
characteristic curve
point 2
The lower limit is defined
by parameter
PFAbsMin.
0.5 to 1
‒
0.8
Excitation of the
displacement power
factor cos φ at
characteristic curve
point 2
OvExt
Overexcited
OvExt
UnExt
Underexcited
Specifies the feed-in
capacity in % at
characteristic curve
point 1
0% to 90%
‒
0%
Specifies the feed-in
capacity in % at
characteristic curve
point 2
10% to 100%
‒
100%
Name
Description
Value/range
Explanation
Default