13 Parameters
SMA America, LLC
102
SCCP-US-BE-US_en-52
Operating Manual
Tripping time at
undervoltage level 1
160 ms to
2,000 ms
Parameter value specified by
IEEE 1547. Do not operate
using a different parameter
value unless directed by the
utility.
2,000 ms
VCtlllLim**
Limiting value for
undervoltage release level 2
50% to 96%
{0% to 100%}
Parameter range specified by
IEEE 1547. Do not operate
outside the standard range
unless directed by the utility.
50%
Tripping time at
undervoltage level 2
160 ms to
1,000,000 ms
‒
160 ms
[200 ms]
Limiting value for
undervoltage release level 3
0% to 100%
‒
0%
Tripping time at
undervoltage level 3
0 ms to
1,000,000 ms
‒
0 ms
VCtllCharEna*
Activation of dynamic
undervoltage detection
Off
Off
On
VCtllCharTm*
Start time dynamic
undervoltage detection
0 ms to
1,000,000 ms
‒
77 ms
Overvoltage limiting value
120% to 150% ‒
134%
VCtlPeakMaxTm*
Tripping time overvoltage
0 ms to 20 ms
‒
1 ms
VCtlOpMinNom*
Minimum connection voltage
0% to 100%
‒
95%
VCtlOpMaxNom*
Maximum connection
voltage
100% to 200% ‒
106%
HzCtlOpMin*
Minimum connection
frequency
55 Hz to 60 Hz
[45 Hz to 50 Hz]
‒
59.5 Hz
[49.5 Hz]
Maximum connection
frequency
60 Hz to 65 Hz
[50 Hz to 55 Hz]
‒
60.5 Hz
[50.5 Hz]
HzCtlOpMaxRecon* Maximum connection
frequency after grid error
60 Hz to 65 Hz
[50 Hz to 55 Hz]
‒
60.5 Hz
[50.5 Hz]
HzCtlMax*
Threshold for overfrequency
level 3
60 Hz to 66 Hz
[50 Hz to 56 Hz]
‒
60 Hz
[50 Hz]
Tripping time for
overfrequency level 3
0 ms to
1,000,000 ms
‒
0 ms
HzCtlhhLim*
Threshold for overfrequency
level 2
60 Hz to 66 Hz
[50 Hz to 56 Hz]
‒
65 Hz
[55 Hz]
HzCtlhhLimTm*
Tripping time for
overfrequency level 2
0 ms to
1,000,000 ms
‒
100 ms
Name
Description
Range
Explanation
Default
value