13  Parameters

SMA America, LLC

94

SCCP-US-BE-US_en-52

Operating Manual

QoDQ-VArMod**

Specifies the reactive

power setpoint mode in

the operating state

"Q at Night"

Off

Sets reactive power to

0 kVAr and displacement

power factor cos φ to 1

VArCtlCom

Specifies the reactive

power via an external

control unit, such as the

Power Reducer Box

VArCnst

Specifies reactive power

in kVAr via the parameter

QoDQ-VAr

VArCnstNom

Specifies reactive power

in % via the parameter

QoDQ-VArNom

VArCnstNomAnIn

The reactive power

setpoint is imported via an

analog input.

VArCtlVol

Specifies the reactive

power depending on the

line voltage

VArCtlVolHystDb

Specifies the reactive

power depending on the

line voltage (Q = f(V)

characteristic curve)

Q-VAr

Reactive power in kVAr

-550 kVAr to +550 kVAr SC 500CP-US-10

0

-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10

QoDQ-VAr**

Reactive power in kVAr in

the operating state "Q at

Night"

-300 kVAr to +300 kVAr SC 500CP-US-10

0 kVAr

-300 kVAr to +300 kVAr SC 500CP-US-10 600V
-378 kVAr to +378 kVAr SC 630CP-US-10
-432 kVAr to +432 kVAr SC 720CP-US-10
-450 kVAr to +450 kVAr SC 750CP-US-10
-480 kVAr to +480 kVAr SC 800CP-US-10
-510 kVAr to +510 kVAr SC 850CP-US-10
-540 kVAr to +540 kVAr SC 900CP-US-10

Q-VArNom

Reactive power in %

− 100% to +100%

0

Name

Description

Value/range

Explanation

Default

value