13 Parameters
SMA America, LLC
94
SCCP-US-BE-US_en-52
Operating Manual
QoDQ-VArMod**
Specifies the reactive
power setpoint mode in
the operating state
"Q at Night"
Off
Sets reactive power to
0 kVAr and displacement
power factor cos φ to 1
VArCtlCom
Specifies the reactive
power via an external
control unit, such as the
Power Reducer Box
VArCnst
Specifies reactive power
in kVAr via the parameter
QoDQ-VAr
VArCnstNom
Specifies reactive power
in % via the parameter
QoDQ-VArNom
VArCnstNomAnIn
The reactive power
setpoint is imported via an
analog input.
VArCtlVol
Specifies the reactive
power depending on the
line voltage
VArCtlVolHystDb
Specifies the reactive
power depending on the
line voltage (Q = f(V)
characteristic curve)
Q-VAr
Reactive power in kVAr
-550 kVAr to +550 kVAr SC 500CP-US-10
0
-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10
QoDQ-VAr**
Reactive power in kVAr in
the operating state "Q at
Night"
-300 kVAr to +300 kVAr SC 500CP-US-10
0 kVAr
-300 kVAr to +300 kVAr SC 500CP-US-10 600V
-378 kVAr to +378 kVAr SC 630CP-US-10
-432 kVAr to +432 kVAr SC 720CP-US-10
-450 kVAr to +450 kVAr SC 750CP-US-10
-480 kVAr to +480 kVAr SC 800CP-US-10
-510 kVAr to +510 kVAr SC 850CP-US-10
-540 kVAr to +540 kVAr SC 900CP-US-10
Q-VArNom
Reactive power in %
− 100% to +100%
‒
0
Name
Description
Value/range
Explanation
Default
value