11  Troubleshooting

SMA America, LLC

80

SCCP-US-BE-US_en-52

Operating Manual

11.4.2 Error Numbers 01xx to 13xx - Disturbance on the Utility Grid

After a grid failure, the inverter monitors the utility grid for a specific period until it is reconnected.
If the inverter monitors the utility grid after a grid error, the grid monitoring time is maintained.
Certain errors, such as grid errors, cause the inverter to shut down. In this case, the instantaneous value TmsRmg indicates

the time during which the inverter monitors the electricity grid until it is reconnected. This grid monitoring time can be

defined in parameter GdErrTm.

Corrective

measures

The corrective measures specify measures that can help you

rectify the error.

Error no.

Explanation

Behavior of the

inverter

Corrective measures

S 1

S 2

R

0103*

Line voltage is too high. Overvoltage

detected by redundant monitoring.

30 s 30 s

• Check the line voltage.
• Check the grid connection.
• Check whether the utility grid is

stable.

• Make sure the external fuses

function properly.

• Make sure the AC cable

connections are securely

connected.

0104*

Line voltage is too high. Overvoltage

detected by standard monitoring.

C

C

0203*

Line voltage is too low. Undervoltage

detected by redundant monitoring.

30 s 30 s

0204*

The line voltage is too low. Undervoltage

detected by standard monitoring.

30 s 30 s

0205*

A line conductor of the electricity grid has

failed.

30 s 30 s

0502*

Power frequency is too low. Power

frequency fault detected by standard

monitoring.

30 s 30 s

• Check power frequency.
• Check the grid monitoring relay

display.

• Make sure the fuses in the load

circuit function properly.

0503*

Power frequency is too high. Power

frequency fault detected by standard

monitoring.

30 s 30 s

0504*

Power frequency is too low. Power

frequency fault detected by redundant

monitoring.

30 s 30 s

0505*

Power frequency is too high. Power

frequency fault detected by redundant

monitoring.

30 s 30 s

0506*

The inverter has detected a stand-alone

grid and disconnected from the electricity

grid.

W

W

• Check power frequency.

0801

One line conductor of the utility grid has

failed.

30 s 30 s

• Check the line voltage.
• Make sure the external fuses

function properly.

• Make sure the AC cable

connections are securely

connected.

0802*

Information

Level

Behavior

Explanation