11 Troubleshooting
SMA America, LLC
80
SCCP-US-BE-US_en-52
Operating Manual
11.4.2 Error Numbers 01xx to 13xx - Disturbance on the Utility Grid
After a grid failure, the inverter monitors the utility grid for a specific period until it is reconnected.
If the inverter monitors the utility grid after a grid error, the grid monitoring time is maintained.
Certain errors, such as grid errors, cause the inverter to shut down. In this case, the instantaneous value TmsRmg indicates
the time during which the inverter monitors the electricity grid until it is reconnected. This grid monitoring time can be
defined in parameter GdErrTm.
Corrective
measures
‒
‒
The corrective measures specify measures that can help you
rectify the error.
Error no.
Explanation
Behavior of the
inverter
Corrective measures
S 1
S 2
R
0103*
Line voltage is too high. Overvoltage
detected by redundant monitoring.
30 s 30 s
‒
• Check the line voltage.
• Check the grid connection.
• Check whether the utility grid is
stable.
• Make sure the external fuses
function properly.
• Make sure the AC cable
connections are securely
connected.
0104*
Line voltage is too high. Overvoltage
detected by standard monitoring.
C
C
‒
0203*
Line voltage is too low. Undervoltage
detected by redundant monitoring.
30 s 30 s
‒
0204*
The line voltage is too low. Undervoltage
detected by standard monitoring.
30 s 30 s
‒
0205*
A line conductor of the electricity grid has
failed.
30 s 30 s
‒
0502*
Power frequency is too low. Power
frequency fault detected by standard
monitoring.
30 s 30 s
‒
• Check power frequency.
• Check the grid monitoring relay
display.
• Make sure the fuses in the load
circuit function properly.
0503*
Power frequency is too high. Power
frequency fault detected by standard
monitoring.
30 s 30 s
‒
0504*
Power frequency is too low. Power
frequency fault detected by redundant
monitoring.
30 s 30 s
‒
0505*
Power frequency is too high. Power
frequency fault detected by redundant
monitoring.
30 s 30 s
‒
0506*
The inverter has detected a stand-alone
grid and disconnected from the electricity
grid.
W
W
‒
• Check power frequency.
0801
One line conductor of the utility grid has
failed.
30 s 30 s
‒
• Check the line voltage.
• Make sure the external fuses
function properly.
• Make sure the AC cable
connections are securely
connected.
0802*
Information
Level
Behavior
Explanation