beautypg.com

SMA SC 500CP-US-10 600V User Manual

Page 92

background image

13  Parameters

SMA America, LLC

92

SCCP-US-BE-US_en-52

Operating Manual

Qmax**

Limitation of the reactive

power of the inverter

0 kVAr to 550 kVAr

SC 500CP-US-10

550 kVAr

0 kVAr to 550 kVAr

SC 500CP-US-10 600V

550 kVAr

0 kVAr to 700 kVAr

SC 630CP-US-10

700 kVAr

0 kVAr to 792 kVAr

SC 720CP-US-10

792 kVAr

0 kVAr to 825 kVAr

SC 750CP-US-10

825 kVAr

0 kVAr to 880 kVAr

SC 800CP-US-10

880 kVAr

0 kVAr to 935 kVAr

SC 850CP-US-10

935 kVAr

0 kVAr to 990 kVAr

SC 900CP-US-10

990 kVAr

QoDQmax**

Limitation of the reactive

power of the Sunny

Central in the operating

state "Q at Night"
The reactive power

cannot exceed Qlimit.

0 kVAr to 300 kVAr

SC 500CP-US-10

300 kVAr

0 kVAr to 300 kVAr

SC 500CP-US-10 600V

300 kVAr

0 kVAr to 378 kVAr

SC 630CP-US-10

378 kVAr

0 kVAr to 432 kVAr

SC 720CP-US-10

432 kVAr

0 kVAr to 450 kVAr

SC 750CP-US-10

450 kVAr

0 kVAr to 480 kVAr

SC 800CP-US-10

480 kVAr

0 kVAr to 510 kVAr

SC 850CP-US-10

510 kVAr

0 kVAr to 540 kVAr

SC 900CP-US-10

540 kVAr

PFAbsMin*

Limitation of the

displacement power

factor cos φ

0.5 to 1

0.8

Name

Description

Value/range

Explanation

Default

value