3 monitoring the power frequency – SMA SC 500CP-US-10 600V User Manual

Page 73

background image

SMA America, LLC

9  Grid Monitoring

Operating Manual

SCCP-US-BE-US_en-52

73

Figure 35: Parameters for monitoring the line voltage

For the setting ranges of the voltage limiting values, see Section 13.1.2.

Procedure:

1. Log in to the user interface.
2. Enter the installer password in the appropriate field on the homepage and confirm with [Login].
3. If necessary, change the limiting value of the undervoltage in the parameter VCtlllLim (see Section 6.2, page 51).
4. If necessary, change the limiting value of the overvoltage in the parameter VCtlhhLim (see Section 6.2, page 51).
5. End the entering of parameters with [Save].

9.3 Monitoring the Power Frequency

For the power frequency monitoring, two limiting values are defined for the minimum power frequency and one limiting

value is defined for the maximum power frequency in accordance with IEEE 1547. Do not operate using a different

parameter value unless directed by the utility.

Parameter

Explanation

Default 60 Hz value

[50 Hz value]

VCtlllLim

The second threshold of the undervoltage

50%

VCtlllLimTm

Time period for the second limiting value for undervoltage

160 ms [200 ms]

VCtllLim

The first threshold of the undervoltage

88%

VCtllLimTm

Time period for the first limiting value for undervoltage

2,000 ms

VCtlhLim

The first threshold of the overvoltage

110%

VCtlhLimTm

Time period for the first limiting value for overvoltage

1,000 ms

VCtlhhLim

The second threshold of the overvoltage

120%

VCtlhhLimTm

Time period for the second limiting value for overvoltage

160 ms [200 ms]