13 Parameters
SMA America, LLC
98
SCCP-US-BE-US_en-52
Operating Manual
Q-VArSubVal
Replacement value for
the reactive power
setpoint outside of
normal feed-in operation
during communication
disturbance
-550 kVAr to +550 kVAr SC 500CP-US-10
0 kVAr
-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10
PF-PFSubVal
Replacement value for
cos φ outside of normal
feed-in operation during
communication
disturbance
0.9 to 1
‒
1
PF-PFExtSubVal
Replacement value of
excitation type during
communication
disturbance
OvExt
Overexcited
OvExt
UnExt
Underexcited
P-WSubValRun
Replacement value of
active power limitation
outside of normal feed-in
operation during
communication
disturbance
0 kW to 1,000 kW
‒
990 kW
Q-VArSubValRun
Replacement value of
reactive power setpoint
for normal feed-in
operation during
communication
disturbance
-550 kVAr to +550 kVAr SC 500CP-US-10
0 kVAr
-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10
Voltage value at which
the Q(V) characteristic
curve is activated, in %
relative to the nominal
voltage
0% to 100%
‒
0%
Voltage value at which
the Q(V) characteristic
curve is deactivated, in %
based on the nominal
voltage
0% to 100%
‒
0%
Name
Description
Value/range
Explanation
Default
value