13  Parameters

SMA America, LLC

98

SCCP-US-BE-US_en-52

Operating Manual

Q-VArSubVal

Replacement value for

the reactive power

setpoint outside of

normal feed-in operation

during communication

disturbance

-550 kVAr to +550 kVAr SC 500CP-US-10

0 kVAr

-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10

PF-PFSubVal

Replacement value for

cos φ outside of normal

feed-in operation during

communication

disturbance

0.9 to 1

1

PF-PFExtSubVal

Replacement value of

excitation type during

communication

disturbance

OvExt

Overexcited

OvExt

UnExt

Underexcited

P-WSubValRun

Replacement value of

active power limitation

outside of normal feed-in

operation during

communication

disturbance

0 kW to 1,000 kW

990 kW

Q-VArSubValRun

Replacement value of

reactive power setpoint

for normal feed-in

operation during

communication

disturbance

-550 kVAr to +550 kVAr SC 500CP-US-10

0 kVAr

-550 kVAr to +550 kVAr SC 500CP-US-10 600V
-700 kVAr to +700 kVAr SC 630CP-US-10
-792 kVAr to +792 kVAr SC 720CP-US-10
-825 kVAr to +825 kVAr SC 750CP-US-10
-880 kVAr to +880 kVAr SC 800CP-US-10
-935 kVAr to +935 kVAr SC 850CP-US-10
-990 kVAr to +990 kVAr SC 900CP-US-10

Q-VLockInW**

Voltage value at which

the Q(V) characteristic

curve is activated, in %

relative to the nominal

voltage

0% to 100%

0%

Q-VLockOutW**

Voltage value at which

the Q(V) characteristic

curve is deactivated, in %

based on the nominal

voltage

0% to 100%

0%

Name

Description

Value/range

Explanation

Default

value