beautypg.com

4 continuity testing, Incoming circuits, Continuity testing – Welltech Dialogic SS7 Protocols ISUP User Manual

Page 95: Continuity

background image

Dialogic

®

SS7 Protocols ISUP Programmer's Manual Issue 15

95

6.8.4 Continuity

Testing

Incoming circuits

There are two situations where continuity checks on incoming circuits may
occur:

• When a Continuity check request (CCR) message is received for an idle

circuit.

• When a continuity check is performed on an incoming circuit during call

set up.

In order to support continuity checks on idle circuits, the Circuit seized

indication (SZE) primitive is used. This primitive is not defined by ITU or

ANSI but is used by the ISUP module to indicate that the circuit has been

seized and the format of this primitive is described in

Section

:

6.6.4 Circuit

Seized Indication on page 60

. The Circuit seized indication is sent by ISUP to

the application to indicate that the circuit is in use but the call cannot be

routed at present.

On receipt of the Circuit seized indication, the application should mark the

circuit as being busy so that it is not available for selection for an outgoing

call). One way of achieving this would be to introduce a “circuit seized” state
in the application. The application should remain in this state until either a

Setup indication is received (in which case the call should proceed as normal)

or else a Release indication is received (in which case the call is released as

described in

Section

:

6.8.1 Call Clearing Procedure on page 90

).

The following subsections show a number of different example scenarios

where a continuity check is made on an incoming circuit.

See Section

8.3:

Configure Timers Request on page 136

for details.