ATEIS DIVA8G2 User Manual
Page 270

DIVA system
270
© 2012 ATEÏS
Virtual point command
Fire Panel sends the following message if it wants to activate or deactivate an evacuation input on
Voice Alarm System.
Command FP “>” “I” “V” “C” “PN2” “VN3” “SP” “VC3” “CS2” “CR” “LF”
Response VAS “>” “I” “V” “P” “VN3” “SP” “VS3” “SP” “00000” “CR”
With
PN2 Panel Number 2 characters (value 0)
VN3 Evacuation Input 3 characters
SP ASCII Space 1 character (value 0x20)
VC3 Command Code 3 characters
CS2 Checksum 2 characters
VS3 Status Code 3 characters
If the Command Code is 001 or 002, the Voice Alarm System will give no response, because of the fact
that these messages are only informative messages.
Messages with Command Code 005 will not be interpreted. Only the “Mode 1” should be used to activate
an Evacuation Input.
If the Command Code is 006 and the Evacuation Input is 000, the number of Voice Alarm System
responses depends on the number of faulty Evacuation Inputs.
Command Code Description
000
No action, enquire status only
001
Evacuation Input has been enabled – informative only
002
Evacuation Input has been disabled – informative only
003
Deactivate the Evacuation Input
004
Activate the Evacuation Input (Mode 1)
005
Activation in mode will not be interpreted
006
Retransmit fault or unavailable message(s) for the Evacuation Input(s)
Status Code Description
000
Evacuation Input not defined within Voice Alarm System
001
Evacuation Input inactive
002
Evacuation Input waiting to go inactive after deactivate command
003
Evacuation Input request to go inactive denied
004
Evacuation Input active (mode 1)
005
Evacuation Input waiting to go inactive after activate command
006
Evacuation Input request to go active denied
Status change message
Voice Alarm System sends this message in case of Evacuation Input status change (fault or out of
fault, unavailable or returned to available).
Message VAS “>” “I” “V” “P” “VN3” “SP” “VS3” “SP” “00000” “CR”
Response FP “>” “I” “A” “C” “K” “CR” “LF”