3 clearances, Mounting, 1 approximate weights – Reznor MAPS II Unit Installation Manual User Manual
Page 9: 1 accessory weights

Form I-MAPS II, P/N 206131 (Rev 13), Page 9
4.3 Clearances
Provide minimum clearances as shown in
FIGURE 3. Minimum clearances are
required to ensure proper operation and access for service. If a heat section is
included, clearances to combustibles are required. Clearance to combustibles
is defined as the minimum distance from the heater to a surface or object that
is necessary to ensure that a surface temperature of 90°F above the surround-
ing ambient temperature is not exceeded.
The area above the condenser fans MUST always be totally open space.
����������������
���������������
����������
�������
�������������
�����������
������������������������������
�������������������������
�������������������������������
�������
�������������������
������������������
��������������������������������������������������������������
�����������������������������������������������������������������������
�������������������������������
���������
���������
���
����������
��������������
�������
�������
�������������������������
�����������������������
�����������������������
�����������������������
�������������������������
����������������������������
���������������������������
FIGURE 3 -
Clearances
Additional Heat Section Clearance Information
Gas Heat Section - If installing a Model RDCA or RDDA, the 4 ft (1.22M) service clearance provides for
clearance to combustibles and required space for combustion air inlet and venting.
Vent terminal must be 4 feet (1.22M) from gas and electric meters, regulators, and relief equipment.
Electric Heat Section - If installing a Model RECA or REDA, provide a 4 ft (1.22M) service clearance.
5. Mounting
5.1 Approximate
Weights
Accessory Weights (add to system weight in tables on page 10 or 11)
Cabinet Size
A
B
C
Optional Accessory
lbs
kg
lbs
kg
lbs
kg
Outside Air Hood (Option AS16 or AS19)
35
16
45
20
80
36
Model JHUP-0250 Curb Duct Furnace
530 240
Downflow Roof Curb (Option CJ31)
93
42
105
48
235 107
32" (813mm) High Horizontal Flow Roof Curb (Option CJ50)
210
95
240 109 530 240
36" (914mm) High Horizontal Flow Roof Curb (Option CJ49)
575 261
5.1.1 Accessory Weights
Refer to the system weight charts on page 10 or 11
to determine Cabinet Size.
Add the accessory weight to the system weight for model and size.
Optional building power exhaust is not listed because weight varies with motor
horsepower. Additional motor only weight would be from 23-70 lbs (10-32 kg).