3 warranty, 4 installation codes, 3 warranty 1.4 installation codes – Reznor MAPS II Unit Installation Manual User Manual
Page 4: Location, Receiving, moving, and storage 1. general (cont'd)

Form I-MAPS II, Page 4
1.3 Warranty
Refer to limited warranty information on the warranty form in the "Literature
Bag" shipped with this system. If an optional extended warranty applies, keep
the extended warranty information for future reference and verification of war-
ranty.
Massachusetts
Requirements
If being installed in the Commonwealth of Massachusetts, this unit must be
installed by a licensed plumber or licensed gas fitter.
California Warning
Label
If a gas-fired heat section is included and the system is being installed in the
state of California, the installer MUST attach a warning label on the outside of
the heat section access panel. The California Warning label is shipped in the
"Literature Bag". If installation is in California, select a dry, clean location on the
heat section access panel and adhere the label.
3. Receiving,
Moving, and
Storage
1. General (cont'd)
1.4 Installation Codes
These packaged systems are certified by ITS to Heating Cooling Equipment
(latest edition), UL 1995 / CAN/CSA C22.2 No. 236. Electrical characteristics
are shown on the system rating plate. All cooling and dehumidification reheat
cycle circuits are factory-charged with R-22 or R407C refrigerant.
Model RDCA and Model RDDA include a gas heat section. The system
includes a power-vented gas-fueled duct furnace. The gas-fired furnace using
the Reznor
®
T
CORE
2®
combustion system is available in 13 sizes from 100 to
700 MBH for use with either natural or propane gas. The furnace is certified by
ITS to both ANSI Z83.8b and CSA 2.6b-M. The ETL label, type of gas, and the
firing rate are shown on the heat section rating plate.
Model RECA and Model REDA include an electric heat section. The electric
heat section is available in 21 sizes from 5 to 88 kw with single or three-stage
control. Refer to the system rating plate for electrical requirements. Models
RECA and REDA require only a single-point electrical supply.
Approval and
Installation Codes
2. Location
All of these packaged systems are designed to be mounted on a roof or slab
using a manufacturer designed curb. Both downflow and horizontal curbs are
available.
When the unit is being placed on a roof, location depends on the roof struc-
ture.
Position the curb so that the air inlet of the unit will not be facing into the pre-
vailing wind.
Always comply with the clearances in Paragraph 4.3.
For condensate drainage and proper operation, it is important the installation
be level.
This system was test operated and inspected at the factory prior to crating
and was in operating condition. If the equipment has incurred any damage in
shipment, document the damage with the carrier and immediately contact your
Reznor distributor.
3.1 Receiving and Moving