beautypg.com

3 disconnect switch, 4 control wiring, 3 disconnect switch 7.4 control wiring – Reznor MAPS II Unit Installation Manual User Manual

Page 25

background image

Form I-MAPS II, P/N 206131 (Rev 13), Page 25

Voltage

The electric supply to the unit must meet stringent requirements for the system

to operate properly. Voltage supply and voltage imbalance between phases

should be within the tolerances listed below. If the power is not within these

voltage tolerances, contact the power company prior to operating the system.

Voltage Supply - See voltage use range on the rating plate. Measure (and

record) each supply leg voltage at all line disconnect switches. Readings must

fall within the allowable range on the rating plate.

Voltage Imbalance - In a 3-phase system, excessive voltage imbalance

between phases will cause motors to overheat and eventually fail. Maximum

allowable imbalance is 2%. To determine voltage imbalance, use recorded

voltage measurements in this formula.

NOTE: If the system

was ordered with a volt-

age loss safety switch

(Option BF14,

FIGURE

16B) that monitors volt-

age balance, the circuit

to the compressors will

be opened in the event of

voltage imbalance. In six

minutes, the switch will

recheck the circuit. If the

problem is eliminated, the

circuit will be re-activated.

Key: V1, V2, V3 = line voltages as measured Formula:

VA (average) =

(V1 + V2 + V3)

3

% Voltage Imbalance = [100 x (VA - VD)]

VA

VD = Line voltage (V1, V2, or V3) that

deviates farthest from average

7.3 Disconnect

Switch

FIGURE 13 - Built-in,

non-fusible, lockable

Disconnect Switch

NOTE: Illustration

shows disconnect used

for cooling only and

cooling with a gas heat

section. Cooling with

electric heat requires a

larger disconnect.

The system is equipped with a built-in non-fusible, lockable disconnect switch

(

FIGURE 13). If an additional optional fusible disconnect is ordered, it will be

shipped separately for field installation (or may be field supplied).
When running electrical conduit, be careful that it is clear of all access panels.

The built-in disconnect switch requires copper wiring with ampacity based on

60°C maximum temperature rating at the line side terminals.
If field installing an additional disconnect switch, it is recommended that there

is at least four feet (1.2M) of service room between the switch and system

access panels. When providing or replacing fuses in a fusible disconnect, use

dual element time delay fuses and size according to the rating plate.

DANGER: To prevent injury or death due to electrocution or

contact with moving parts, lock disconnect switch open. See

Hazard Levels, page 2.

WARNING: If an optional gas furnace is included, if you turn

off the power supply, turn off the gas.

7.4 Control Wiring

Field Control Wiring Length/Gauge

Total Wire

Length

Distance from Unit

to Control

Minimum

Recommended Wire

Gauge

ft

M

ft

M

150

46

75

23

18

250

76

125

38

16

350

107

175

53

14

Wire 24 volt controls accord-

ing to the wiring diagram.

Refer to the chart on the

right for minimum control

wire gauge by length.

Digital control inputs are low-current, resistance-based signals. The manu-

facturer recommends for optimum temperature control performance that the

analog and digital inputs (zone sensors, discharge air sensors, etc.) that are

connected to the FX05 or FX06 controller be routed in one of the following

manners:

• In separate conduits, isolated from 24VAC controls and line voltage power

to the unit; OR

• If the wires are to be run in the same conduit as the 24 VAC control wir-

ing, the sensor wiring must use shielded cable and be bundled separately

from 24 VAC control wiring. The shield must be drained at the unit and

taped on the opposite end.

Digital Control Wiring

Wire

Gauge

Maximum Sensor

Wire Length

(Digital Control)

AWG

Feet

Meters

14

800

244

16

500

152

18

310

94

20

200

61

22

124

38

NOTE: If wire is included with the digital sensor, it is 22 AWG.