Form I-MAPS II, P/N 206131 (Rev 13), Page 61

Saturation

Temperature Pressure (psig)

(ºF)

(ºC)

R-22 R-407C

0

-17.8

24

19.5

5

-15.0

28.2

23.6

10

-12.2

32.7

28.0

15

-9.4

37.7

32.7

20

-6.7

43

37.9

25

-3.9

48.7

43.6

30

-1.1

54.9

49.6

35

1.7

61.4

56.2

40

4.4

68.5

63.2

45

7.2

76

70.7

50

10.0

84

78.8

55

12.8

92.5

87.5

60

15.6

101.6

96.8

65

18.3

111

106.7

70

21.1

121.4

117.2

75

23.9

132

128.4

80

26.7

144

140.4

85

29.4

156

153.1

90

32.2

168.4

166.5

95

35.0

182

180.8

100

37.8

196

195.8

105

40.6

211

211.8

110

43.3

226.4

228.7

115

46.1

243

246.5

120

48.9

260

265.3

125

51.7

278.4

285.2

130

54.4

296.8

306.1

135

57.2

317

328.2

140

60.0

337.3

351.4

145

62.8

359

375.9

Pressure/

Temperature Chart

for Checking

Superheat and

Subcooling