Receiving, moving, and storage, 1 receiving and moving, Reznor – Reznor MAPS II Unit Installation Manual User Manual
Page 5: Rca or rda, Suitable for outdoor use, Rating plate

Form I-MAPS II, P/N 206131 (Rev 13), Page 5
FIGURE 1A - Sample of System Rating Plate (applies to all models)
System Rating Plate Key:
A = Model
B = Manufacturing Date (Month/Year)
C = Blower Motor HP
D = Volts/Phase/Hertz
E = Full Load Amps of Blower Motor
F = Minimum Circuit Ampacity
G = Maximum Fuse Size
H = Quantity - Compressor A
I = Rated Load Amps of Compressor A
J = Locked Rotor Amps of Compressor A
K = Quantity - Compressor B
L = Rated Load Amps of Compressor B
M = Locked Rotor Amps of Compressor B
N = Quantity - Compressor C
O = Rated Load Amps of Compressor C
P = Locked Rotor Amps of Compressor C
Q = Quantity - Compressor D
R = Rated Load Amps of Compressor D
S = Locked Rotor Amps of Compressor D
T = Quantity Condenser Fan Motors
U = Rated Load Amps of Condenser(s)
V = Refrigerant Charge (lbs) - Circuit A
W = Refrigerant Charge (lbs) - Circuit B
X = Refrigerant Charge (lbs) - Circuit C
Y = Refrigerant Charge (lbs) - Circuit D
Z = Condenser Fan Motor HP
AA = Test Pressure High (psig)
BB = Test Pressure Low (psig)
CC = SCFM Airflow
DD = External Static Pressure (" w.c.)
EE = Drive (Option AM)
FF = Wiring Diagram No.
RCA or RDA
MADE IN USA
FOR INDUSTRIAL/COMMERCIAL USE ONLY
SUITABLE FOR OUTDOOR USE
MODEL [ A ]
[ B ]
SERIAL NO. [
]
[D] VOLTS +/- 10% [D] PHASE [D] HZ
MINIMUM CIRCUIT AMPACITY(MCA)
[ F ] AMPS
MAXIMUM FUSE SIZE/*CKT BREAKER
[ G ] AMPS
QTY
FLA(EA)
HP(EA)
SUPPLY AIR BLOWER MOTOR
1
[ E ]
[ C ]
CONDENSER FAN MOTOR (S)
[ T ]
[ U ]
[ Z ]
QTY
RLA (EA)
LRA (EA)
COMPRESSOR(S) A
[ H ]
[ I ]
[ J ]
COMPRESSOR(S) B
[ K ]
[ L ]
[ M ]
COMPRESSOR(S) C
[ N ]
[ O ]
[ P ]
COMPRESSOR(S) D
[ Q ]
[ R ]
[ S ]
CIRCUITS
A
B
C
D
REFRIGERANT - [ ] CHARGE - LBS
[ V ]
[ W ]
[ X ]
[ Y ]
TEST PRESSURES
HIGH [AA] PSIG LOW [BB] PSIG
EQUIPPED FOR OPERATION AT AN AIR FLOW OF [
CC ] SCFM
AGAINST A STATIC PRESSURE OF [ DD ] INCHES WATER COLUMN.
DRIVE RPM [ EE ]
WIRE DIAGRAM [ FF ]
REFER TO RATING PLATE IN THE FURNACE SECTION (WHEN USED)
FOR ADDITIONAL INFORMATION.
*HACR TYPE REQUIRED PER NEC
ELECTRICAL
REZNOR
MERCER, PA., U.S.A. 16137
Check the entire unit for damage paying particular attention to the structural
integrity of both the points of attachment of the lifting lugs and the condenser
fan section.
•
Lifting Lugs - Inspect the points of attachment of the lifting lugs.
•
Condenser Fan Section - On the side of the system, check the condenser
fan guards and the fan blades.
IMPORTANT NOTE: Sizes 176, 226, 230, 280, 292, 346, 374, 428, and
446 have a "C" Size Cabinet and MUST be loaded and unloaded
using all six lifting lugs with a spreader bar. DO NOT attempt to
move a "C" size cabinet system with a fork lift.
On the inside of the door of the high voltage electrical compartment, locate the
system rating plate (See
FIGURE 1A, below, and FIGURE 2A or 2B, page 7 or
8). Check the specifications and the electrical characteristics and verify com-
patibility with the electric supply at the installation site. Check fuses/breakers
for correct sizing.
If installing a Model RDCA, RDDA, RECA, or REDA, check the rating plate on
the inside cover of the heat section. Be sure that the rating plate information
is compatible with the electric and/or gas supply at the installation site. (See
FIGURE 1B for a sample of a gas-fired heat section rating plate.)
Rating Plate