Technical data – Reznor MAPS II Unit Installation Manual User Manual
Page 59

Form I-MAPS II, P/N 206131 (Rev 13), Page 59
Technical Data
- Applies to Makeup Air Cooling System in Models RCA, RDCA, and RECA
Technical
Data
-
Applies to
Makeup
Air Cooling
System and
Re-Heat Pump
Reheat Cycle
in Models
RDA, RDDA,
and REDA
Cabinet
Size
Model
Size
Capacity
Stages
Compressors
Condensers
Evaporator Coil
Condensate
Drain Size
Nominal
Tons
Qty
Coils
Fans
Face Area Rows FPI
Face Area Rows Qty CFM HP
(Ckt A/B) (A/B) (A/B)
A
060 40/60/100
2.0/3.0
2
5.75
3
1 3490 3/4
5.2
3
14
1" MPT
A&B*
078 30/70/100
2.0/4.5
2
9.6
3
1 3992 3/4
7.3
3
13
1" MPT
A&B*
090 40/60/100
3.0/4.5
2
9.6
3
1 4496 3/4
7.3
3
14
1" MPT
A&B*
108 33/66/100
3.0/6.0
2
11.5
3
1 5000 3/4
7.3
4
13
1" MPT
A&B*
120 42/58/100
4.5/6.0
2
13.4
3
2 7479 3/4
7.3
4
13
1" MPT
A
164 33/66/100 4.5/3.0/6.0 3
17.25
3
2 8487 3/4 7.3 / 7.3 1 / 4 11 / 13
1" MPT
B
166 33/66/100 4.5/3.0/6.0 3
17.25
3
2 8487 3/4
7.3
6
13
1" MPT
C***
176 31/69/100 4.5/10.0
2
23
3
2 10000 1
18.3
3
13
1" MPT
B
184 30/70/100 4.5/4.5/6.0 3
19.1
3
2 8991 3/4
10.9
4
13
1" MPT
B
198 36/64/100 4.5/6.0/6.0 3
21.0
3
2 9475 3/4
10.9
6
13
1" MPT
C***
226 33/66/100 6.2t/6.2t/6.2 3
23
3
2 10000 1
18.3
4
13
1" MPT
C***
292 25/50/100 6.2t/6.2t/12 3
26.7
3
3 13500 1
18.3
5
13
1" MPT
C***
374 33/66/100 10/10/10
3
38.7
3
3 15000 1
18.3
6
13
1" MPT
Sizes (with odd Model number) below are specifically designed for a DRY CLIMATE.
Cabinet
Size
Model
Size
Capacity
Stages
Compressors
Condensers
Evaporator Coil
Condensate
Drain Size
Nominal
Tons
Qty
Coils
Fans
Face Area Rows FPI
Face Area Rows Qty CFM HP
(Ckt A/B) (A/B) (A/B)
A
025
100
2.0
1
5.75
3
1 3490 3/4
5.2
2
7
1" MPT
A
037
100
3.0
1
5.75
3
1 3490 3/4
5.2
2
10
1" MPT
A
059** 40/60/100
2.0/3.0
2
9.6
3
1 4496 3/4 5.2 / 5.2 2 / 2 6 / 6
1" MPT
A
077** 30/70/100
2.0/4.5
2
11.5
3
1 5000 3/4 5.2 / 5.2 2 / 2 7 / 9
1" MPT
A
109** 33/66/100
3.0/6.0
2
17.25
3
2 8487 3/4 5.2 / 5.2 2 / 2 9 / 10
1" MPT
B
139** 37/63/100 4.5/3.0/4.5 3
21.0
3
2 9475 3/4 7.3 / 7.3 2 / 2 12 / 11
1" MPT
* These sizes in cooling only or with an electric heat section are always Cabinet A. With gas heat, cabinet size depends
on heating capacity. ** Models 059, 077, 109, and 139 are rated for up to 125°F 100% outside air.
*** Due to the larger size, do not attempt to move a "C" cabinet system with a fork lift; use the lifting lugs.
Cabinet
Size
Model
Size
Cooling
Capacity
Stages
Cooling
Compressors
Cooling
Condensers Drain
Size
Re-Heat Pump
Compressor(s)
Coil
Condenser
Nominal
Tons
Qty
Fans
Nominal
Tons
Qty Face
Area Rows
Face
Area Rows
Qty CFM HP
A&B*
102
30/70/100
2.0/4.5
2
1 4300 3/4 1" MPT
2
1
7.3
1
7.5
1
A&B*
114
40/60/100
3.0/4.5
2
1 4300 3/4 1" MPT
2
1
7.3
1
7.5
1
A&B*
126
33/66/100
3.0/6.0
2
1 5000 3/4 1" MPT
2
1
7.3
1
7.5
1
A&B*
144
42/58/100
4.5/6.0
2
2 6400 3/4 1" MPT
2
1
7.3
1
7.5
1
B
188
33/66/100
4.5/3.0/6.0
3
2 8200 3/4 1" MPT
2
1
7.3
1
7.5
1
B
220
30/70/100
4.5/4.5/6.0
3
2 9300 3/4 1" MPT
3
1
10.9
1
11.3
1
B
234
36/64/100
4.5/6.0/6/0
3
2 9700 3/4 1" MPT
3
1
10.9
1
11.3
1
C***
230
31/69/100
4.5/10.0
3
2 10000 1 1" MPT
4.5
1
18.3
1
16.9
1
C***
280
33/66/100
6.2t/6.2t/6.2
3
2 10000 1 1" MPT
4.5
1
18.3
1
16.9
1
C***
346
25/50/100
6.2t/6.2t/12
3
3 13500 1 1" MPT
4.5
1
18.3
1
16.9
1
C***
428
33/66/100
10/10/10
3
3 15000 1 1" MPT
4.5
1
18.3
1
16.9
1
C***
446
33/66/100
10/10/10
3
3 15000 1 1" MPT
6.2
1
18.3
1
16.9
1
* These sizes in cooling and reheat only or with electric heat are always Cabinet A. With gas heat, cabinet size depends on
heating capacity. *** Due to the larger size, do not move a "C" cabinet system with a fork lift; use the lifting lugs.