Page 34: Heat sections, 1 inlet air control and energy recovery, Options, Controls (cont'd)

Form I-MAPS II, Page 34
FIGURE 25 - Option BD5, Firestat (200°F),
P/N 42782
Firestat for field installation in either the return air
or outlet air ductwork. Follow instructions supplied
with the control. Follow wiring diagram on the unit.
Comply with local building codes.
FIGURE 26 - Option BC2, 115V Convenience GFI Outlet
(external weatherproof factory-installed outlet requires
separate field-supplied power supply)
115V duplex weatherproof receptacle
includes ground fault protection. Requires
separate field-supplied 115 volt power
supply (transformer not included).
FIGURE 24 - Option SA1,
Smoke Detector, P/N
159553 (field installed)
Photoelectric smoke detector
to be field-installed in ductwork.
Follow instructions supplied
with the control. Follow wiring
diagram on the unit. Comply
with local building codes.
8. Controls (cont'd)
9.1.1 Inlet Air Options
- Dampers and
Damper Controls
FIGURE 27 -
Component
Locations
of Air Control Options
AR1, AR8, AR11,
AR17, AR18, AR23,
and AR27
���
���
���
���
���
���
���
9.1 Inlet Air Control
and Energy
Recovery
Options
The system may be equipped with a variety of air control options including
100% outside air, a variety of damper controls for 100% outside air or outside
air and return air, economizers, and field-installed energy recovery modules.
Air controls including economizers are identified as Option AR on the system
wiring diagram. Energy recovery modules are identified as Option ER. Refer
to the FIGURES and listings below to identify applications and components.
Identify and inspect the inlet air control option on the unit.
9. Optional
Equipment
including Heat
Sections
Optional Equipment (alphabetically listed) ......................Where to Look
Air Control Options, Option AR ..................................Paragraph 9.1.1, pages 34-36
Duct Furnace Curb, Model JHUP .......................................Paragraph 5.3, page 17,
Paragraph 9.4, pages 50-51, plus sections of 9.3
Economizer Options, Option AR2 .....................................Paragraph 9.1.2, page 37
Electric Heat Section (Models RECA/REDA)......................Paragraph 9.5, page 51,
plus throughout manual
Energy Recovery, Option ER (field installed) .............Paragraph 9.1.3, pages 37-38
Gas Heat Section (Models RDCA/RDDA) ..................Paragraph 9.3, pages 39-49,
plus throughout manual
Inlet Air Hood, Opt AS16 or AS19 ................................Paragraph 6.3, pages 20-22
Power Exhaust, Option PE ...........................................Paragraph 9.2, pages 38-39
Roof Curb, Opt CJ31, CJ50, or CJ49 ...........................Paragraph 5.2, pages 12-16
Through-the-Base Electrical Supply Entrance, Opt AVC1 ...Paragraph 7.2, page 24
8.4 Miscellaneous Electrical and Control Options (cont'd)