15 technical data, 1 technical data – EVCO EVF818P9 User Manual
Page 71

EVCO S.p.A.
EVF818 | Installer manual ver. 1.0 | Code 144F818E104
page 71 of 76
15
TECHNICAL DATA
15.1
Technical data
Purpose of the device:
blast chiller controller.
user interface
control module
Execution:
board without cover behind a
Plexiglas sheet.
board without cover.
user interface
control module
Dimensions:
340.0 x 84.0 x 36.5 mm
(13.385 x 3.307 x 3.650 cm;
L x H x P).
166.0 x 116.0 x 44.0 mm
(6.535 x 4.566 x 4.399 cm;
L x H x P).
user interface
control module
Installation:
back panel via studs.
on flat surface, with spacers.
user interface
control module
Protection rating:
IP65.
IP00.
user interface
control module
fixed screw terminal boards
(control module).
removable
screw
terminal
boards (user interface, power
supply, inputs, outputs, except
the
output
for
compressor
management and RS-485 serial
port),
faston
measuring
6.3 mm (0.248 in, compressor
management output), 6-pole
connector (TTL serial port).
Connections:
The
maximum
length
of
the
user
interface
- control module connection is 20 m (65.614 ft).
Temperature of use:
from 0 to 55 °C (from 32 to 131 °F).
Storage temperature:
from -25 to 60 °C (from -13 to 140 F).
Humidity for use:
from 10% to 90% relative humidity without condensate.