EVCO EVF818P9 User Manual
Page 46
EVCO S.p.A.
EVF818 | Installer manual ver. 1.0 | Code 144F818E104
page 46 of 76
d16
0
99
min
0
duration of pre-dripping (only if parameter d1 is set at 1;
the compressor and evaporator fan will be off during pre-
dripping and the defrosting output will remain activated)
Par.
Min.
Max.
Unit
Default
Temperature alarms (9) (10)
A1
0
99
°C/°F (1)
10
cabinet temperature below which the minimum temperature
alarm is activated (relative to the work set-point, i.e. “r10 -
A1” during post blast chilling storage and “r11 - A1” during
post deep freezing storage; (“AL” code); see also
parameter A11 (4)
A2
0
1
- - - -
1
enabling of minimum temperature alarm (“AL” code)
1 = yes
A4
0
99
°C/°F (1)
10
cabinet
temperature
above
which
the
maximum
temperature alarm is activated (relative to the work set-
point, i.e. “r10 +A4” during post blast chilling storage and
“r11 +A4” during post deep freezing storage; (“AH” code);
see also parameter A11 (4)
A5
0
1
- - - -
1
enabling of maximum temperature alarm (“AH” code)
1 = yes
A7
0
240
min
15
temperature alarm delay(“AL” code and “AH” code)
A8
0
240
min
15
maximum temperature alarm delay (“AH” code) from the
conclusion of evaporator fan stop and storage start-up
A10
0
240
min
5
duration of a power cut such to cause the power cut alarm
to be memorised ( “PF” code)when the power is supplied
0 = the alarm will not be signalled
AA
0
240
s
5
duration of buzzer activation on conclusion of blast chilling
and deep freezing
A11
1
15
°C/°F (1)
2
parameters A1 and A4 differential