EVCO EVF818P9 User Manual
Page 44

EVCO S.p.A.
EVF818 | Installer manual ver. 1.0 | Code 144F818E104
page 44 of 76
C1
0
240
min
5
minimum time between two consecutive compressor switch-
ons (3)
C2
0
240
min
3
minimum
time
between
compressor
switch-off
and
successive switch-on (3)
C3
0
240
s
0
compressor switch-on minimum duration
C4
0
240
min
10
duration of compressor switch-off during the cabinet probe
error (“Pr1” code) that occurs during storage; see also
parameters C5 and C9
C5
0
240
min
10
duration of compressor switch-on during the cabinet probe
error (“Pr1” code) that occurs during post blast chilling
storage; see also parameter C4
C6
0
199
°C/°F (1)
80
condenser
temperature
above
which
the
blocked
overheated condenser alarm is activated (“COH” code)
C7
0
199
°C/°F (1)
90
condenser
temperature
above
which
the
blocked
compressor alarm is activated (“CSd” code)
C8
0
15
min
1
blocked compressor alarm delay (“CSd” code) (5)
C9
0
240
min
30
duration of compressor switch-on during the cabinet probe
error (“Pr1” code) that occurs during post deep freezing
storage; see also parameter C4
Par.
Min.
Max.
Unit
Default
Defrosting (6)
d0
0
99
h
8
defrosting interval (7)
0 = defrosting will never be activated at intervals