EVF818 | Installer manual ver. 1.0 | Code 144F818E104

page 44 of 76

C1

0

240

min

5

minimum time between two consecutive compressor switch-

ons (3)

C2

0

240

min

3

minimum

time

between

compressor

switch-off

and

successive switch-on (3)

C3

0

240

s

0

compressor switch-on minimum duration

C4

0

240

min

10

duration of compressor switch-off during the cabinet probe

error (“Pr1” code) that occurs during storage; see also

parameters C5 and C9

C5

0

240

min

10

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post blast chilling

storage; see also parameter C4

C6

0

199

°C/°F (1)

80

condenser

temperature

above

which

the

blocked

overheated condenser alarm is activated (“COH” code)

C7

0

199

°C/°F (1)

90

condenser

temperature

above

which

the

blocked

compressor alarm is activated (“CSd” code)

C8

0

15

min

1

blocked compressor alarm delay (“CSd” code) (5)

C9

0

240

min

30

duration of compressor switch-on during the cabinet probe

error (“Pr1” code) that occurs during post deep freezing

storage; see also parameter C4

Par.

Min.

Max.

Unit

Default

Defrosting (6)

d0

0

99

h

8

defrosting interval (7)

0 = defrosting will never be activated at intervals