beautypg.com

EVCO EVF818P9 User Manual

Page 52

background image

EVCO S.p.A.

EVF818 | Installer manual ver. 1.0 | Code 144F818E104

page 52 of 76

LA

1

247

- - - -

247

device address

Lb

0

3

- - - -

2

baud rate

0 = 2,400 baud

1 = 4,800 baud

2 = 9,600 baud

3 = 19,200 baud

LP

0

2

- - - -

2

parity

0 = none (no parity)

1 = odd

2 = even

Notes:

(1)

the unit of measurement depends on parameter P2

(2)

appropriately set the parameters relative to the regulators after modification of parameter P2

(3)

the time established with the parameter is counted also during the "on" status and during the "stand-by" status

(4)

The parameter differential is 2 °C/4 °F

(5)

on device switch-on (or cycle start), if the condenser temperature is already over that established with

parameter C7, parameter C8 will have no effect

(6)

defrosting is only enabled during pre-cooling, on start-up of blast feeding and at the start-up of deep freezing

(in these last two cases on condition that parameter d4 is set at 1) and during storage

(7)

the device memorises the defrosting interval count every 30 minutes; the modification of parameter d0 has

effect from the conclusion of the previous defrosting interval (or the activation of defrosting in manual mode)

(8)

if on activation of defrosting, the previous compressor switched on at from a time shorter than that established

with parameter d15, the compressor will remain on longer for the fraction of time necessary to complete this

time period

(9)

the temperature alarms are only enabled during storage

(10)

during defrosting. pre-dripping, dripping and evaporator fan standstill, the temperature alarms are not enabled,

on condition that they occurred after activation of defrosting. When the door is open, i.e. if the door micro

switch input is active and the parameter i0 is set at values different to 0, the maximum temperature alarm is

not enabled, on condition that occurred after the door was opened

(11)

if parameter P4 is set at 0, during pre-cooling, blast chilling and deep freezing the evaporator fan will be on and

during storing the device will operate as if parameter F2 it were set at 2

(12)

if parameter P5 is set at 0, the condenser fan will function parallel to the compressor

(13)

the door open is enabled only using the "run" state

(14)

if the door is opened during defrosting or evaporator fan standstill, opening has no effect on the compressor

(15)

modify the parameter during the "stand-by" status to prevent damage to the utility

(16)

if parameter u2 is set at 0, device switch-off will cause the cabinet light to switch off and on successive switch

on the cabinet light will remain off. If parameter u2 is set at 1, device switch-off will not cause the cabinet light

to switch off and on successive switch-on the cabinet light stays on

(17)

the pump down valve is activated when the compressor is switched-on.