EVCO EVF818P9 User Manual
Page 60
EVCO S.p.A.
EVF818 | Installer manual ver. 1.0 | Code 144F818E104
page 60 of 76
Pr3
Condenser probe error.
Solutions:
-
the same as the cabinet probe error (“Pr1” code) but relative to the condenser probe.
Main consequences:
-
the condenser fan will operate parallel to the compressor
-
the overheated condenser alarm (“COH” code) will never be activated
-
the compressor blocked alarm (“CSd” code) will never be activated
-
the alarm output will be activated.
Pr4
Needle probe error 1.
Solutions:
-
the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 1.
ain consequences if parameter P3 is set at 1:
-
if the error occurs during the “stand-by” status, temperature-controlled operating cycles will
be started by time-control
-
if the error occurs during temperature-controlled blast chilling, this will have duration of the
time set by parameter r1
-
if the error occurs during temperature-controlled deep freezing, this will have duration of
the time set by parameter r2
-
if the error occurs during needle probe heating, this operation will be interrupted.
-
the alarm output will be activated.
ain consequences if parameter P3 is set at 2 or at 3:
-
the device will not use needle probe 1.
Pr5
Needle probe error 2.
Solutions:
-
the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 2.
Main consequences:
-
the device will not use needle probe 2.
Pr6
Needle probe error 3.
Solutions:
-
the same as the cabinet probe error (“Pr1” code) but relative to the needle probe 3.
Main consequences:
-
the device will not use needle probe 3.