Analog inputs:

4 inputs of which 2 inputs (non optoisolated, which can be set via
configuration parameter for NTC/Pt 1000 probes and for 0-20
mA/4-20 mA/0-5 V ratiometric transducers) which can be set via
configuration parameter for suction temperature backup
probe/suction pressure backup probe, 1 input (non optoisolated,
which can be set via configuration parameter for NTC/Pt 1000
probes) as suction temperature probe and 1 input (non
optoisolated, which can be set via configuration parameter for
0-20 mA/4-20 mA/0-5 V ratiometric/0-10 V transducers) as suction
pressure probe.

NTC analog inputs (10K Ω @ 25 °C, 77 °F)
Kind of sensor:

ß3435.

Working range:

from -40 to 110 °C (from -40 to

230 °F) for standard NTC probes

from -50 to 150 °C (from -58 to

302 °F) for high temperature NTC

probes

from -50 to 110 °C (from -58 to

230 °F) for fast NTC probes.

Accuracy:

±0.6% of the full scale for standard

and fast NTC probes

±0.5% of the full scale for high

temperature

NTC

probes.

Resolution:

0.1 °C (1 °F).

Conversion time:

100 ms.

Protection: none.

Pt 1000 analog inputs (1K Ω @ 0 °C, 32 °F)
Working range:

from -100 to 400 °C (from -148 to

752 °F).

Accuracy:

±0.5% of the full scale.

Resolution:

0.5 °C (1 °F).

Conversion time:

100 ms.

Protection: none.

0-20 mA/4-20 mA analog inputs
Input resistance:

≤ to 200 Ω.

Accuracy:

±1% of the full scale.

Resolution: 0.01

mA.

Conversion time:

100 ms.

Protection:

none; the maximum current

allowed on each input is 25 mA.