beautypg.com

EVCO EPD4DF3 Installer manual User Manual

Page 12

background image

EVCO S.p.A.

EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344

page 12 of 70

GND

common analog inputs and free of voltage digital inputs

AI1

analog input 1 (which can be set via configuration parameter for NTC/Pt 1000 probes and for
0-20 mA/4-20 mA/0-5 V ratiometric transducers)

AI2

analog input 2 (which can be set via configuration parameter for NTC/Pt 1000 probes and for
0-20 mA/4-20 mA/0-5 V ratiometric transducers)

GND

common analog inputs and free of voltage digital inputs

AI3

analog input 3 (which can be set via configuration parameter for NTC/Pt 1000 probes)

AI4

analog input 4 (which can be set via configuration parameter for 0-20 mA/4-20 mA/0-5 V
ratiometric/0-10 V transducers)


CAN port (not available in model EPD4BX3)
Non optoisolated CAN port, with CANBUS communication protocol.

Terminal

Meaning

CAN+ signal

+

CAN- signal

-

GND ground

-

the maximum number of devices that can make a CAN network (32) depends on the bus load; the bus
load depends on the baud rate of the CANBUS communication and on the kind of device in the network
(for example: a CAN network can be made of a programmable controller, of four I / O expansions and of
four user interfaces with baud rate 500,000 baud)

-

connect the CAN port using a twisted pair

-

do not connect more than four I / O expansions.

For the settings about the CAN port look at chapter 7 “CONFIGURATION”.

Terminal

Meaning

GND ground

VDC

power supply remote user interface (22... 35 VDC, 100 mA max.)