7 manual mode, 8 debugging mode – EVCO EPD4DF3 Installer manual User Manual
Page 23

EVCO S.p.A.
EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344
page 23 of 70
6.7
Manual mode
In manual mode (parameter Pr02 = 1), this permits movement of the valve and bringing it to the percentage value
stored in Manual set-point position (parameter Pr03) using the maximum step rate. In this mode is active also the
control algorithm, but its outputs are unused.
6.8
Debugging mode
The debugger feature is enabled when Pr02 = 2: the valve will move from a Debug minimum position (parameter Prd1)
to a Debug maximum position (parameter Prd2) with the step rate defined by Debug step rate (parameter Prd0).
Internally, the actuated step rate value is clamped to the maximum step rate of the selected valve.