EVCO EPD4DF3 Installer manual User Manual
Page 35

EVCO S.p.A.
EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344
page 35 of 70
Pa30
0
1
- - - -
0
Installer
enable low pressure alarm
1 = yes
Pa31
0.00
45.00
barG
0.00
Installer
low pressure setpoint alarm
Pa32
0.20
1.00
barG
0.30
Installer
low pressure alarm hysteresis
Pa33
0
250
min
3
Installer
low pressure alarm delay
Pa40
0
1
- - - -
0
Installer
enable LOP alarm
1 = yes
Pa41
0.0
10.0
K
1.0
Installer
LOP alarm hysteresis
Pa42
0
250
min
3
Installer
LOP alarm delay
Pa50
0
1
- - - -
0
Installer
enable MOP alarm
1 = yes
Pa51
0.0
10.0
K
1.0
Installer
MOP alarm hysteresis
Pa52
0
250
min
3
Installer
MOP alarm delay
Pa53
0.0
25.0
K
7.0
Installer
MOP maximum dSH applicable
Pa54 0.0 25.0
K
8.0 Installer
MOP
band
Pa55
0
255
10 s
15
Installer
MOP filter time constant
Pa56 0 255 min
10 Installer
MOP
bypass
delay
Pa70
0
1
- - - -
0
Installer
enable main power supply alarm
1 = yes
Pa71
0
60
s
1
Installer
main power supply alarm delay
Pa75
0
1
- - - -
0
Installer
enable backup battery alarm
1 = yes
Pa76
0 60 s
35 Installer
backup
battery
alarm
delay
Par.
Min.
Mas.
Unità
Default
Menu
Valve and driver: refrigerant
equipment