EVDRIVE03 | User manual ver. 3.4 | Code 144EPDE344

page 51 of 70

4

Invalid value for parameter PIA3

5

Invalid value for parameter PIA4

6

PIu1 configured as another Piux

Parameters Piu1, Piu2, Piu3 and Piu4 must

each

7

PIu2 configured as another PIux

have different values, or null.

8

PIu3 configured as another PIux

Checked only if Pcty ≥ 6

9

PIu4 configured as another Piux

10

Contradiction between analog input type

Check parameters Piax and Piux.

(Pia1) and its utilization (Piu1)

11

Contradiction between analog input type

Temperature is measured using probes of

(Pia2) and its utilization (Piu2)

type NTC, pt1000, or scaling; pressure

12

Contradiction between analog input type

is measured using current, tension or scaling

(Pia3) and its utilization (Piu3)

probes.

13

Contradiction between analog input type

Checked only if Pcty ≥ 6

(Pia4) and its utilization (Piu4)

14

Awaiting

AI1

configuration

Wait

15

Awaiting

AI2

configuration

Wait

16

Awaiting

AI3

configuration

Wait

17

Awaiting

AI4

configuration

Wait

18

Awaiting analog inputs configurations

Wait

19

Limit error Xmax probe scaling

20

Limit error Xmax probe scaling

21

No AI configured for primary temperature

Check PIu1, PIu2, PIu3 and PIu4 parameters

or pressure probe input and ensure one is

dedicated

to

the

primary

temperature

probe,

and another to the primary pressure probe.

Checked only if Pcty ≥ 6

9.4

Communication error

A communication error is signalled only if a suitable communication mode is selected (Pr06 ≥ 2), and the
communication alarm is active (Pa01 = 1). Under these conditions, the driver expects the controller to periodically
refresh the Enable valve command (EnaV).
If the refresh does not happen for more than half the time set in Communication alarm delay (Pa02), a warning is
given. If the refresh does not happen for more than the time set in Communication alarm delay (Pa02), the
communication is considered lost and communication alarm is set.
Management of this alarm depends on the mode selected. If Pr06 = 2÷5, a communication alarm state will cause the
valve to be forced to the position determined by Communication error position (Pr48), and will then enter the
Communication alarm (5) until the positioning process has completed and the communication start again. If Pr06 =
6÷9, a communication alarm status will place the valve into standalone mode, and DI1 enable the valve.
When the communication alarm is cleared, the valve will automatically return to the online mode.
The significance of bit 3 and 2 of Alarm status (AlSt) are shown in the following table:
bit3

bit2

Significance

0 0 No

communication

alarm

0 1 Warning
1

0

Communication alarm in standalone mode

1 1 Communication

alarm