9.8.3

LOP

When enabled (Pa40), this alarm is triggered when the evaporation temperature (Te) drop below the LOP threshold
(Pc04, Pp04, Pd04). The condition is signalled in the Algorithm status (AlgS) and, when the timeout (Pa42) expires, an
alarm is set. This protection is most useful during start-up of the machine, when the evaporation temperature is
effectively low. It is possible to optimise this phase by setting a correct value in the valve opening on start-up
parameter (parameter Pc21 or Pp21). When the Te temperature returns within its limits (Pa41 defines the hysteresis),
the alarm and signalling are cleared and the normal regulation algorithm resumes.

9.8.4

MOP

When enabled (Pa50), this alarm is triggered when the evaporation temperature (Te) rise above the MOP threshold
(Pc05, Pp05, Pd05) and activates a specific algorithm for managing the MOP. The condition is signalled in the
Algorithm status (AlgS) and, when the timeout (Pa52) expires, an alarm is set. When the Te temperature returns
within its limits (Pa51 defines the hysteresis), the alarm and its signal are cleared and the normal regulation algorithm
resumes.

9.8.5

LowPressure

When enabled (Pa30), and the evaporation pressure (Pe) falls below the low pressure threshold (Pa31), an warning is
signalled. After the timeout (Pa33) expires, the LP alarm is set. The alarm and its signal are cleared automatically
when the pressure returns above the threshold. (Pa32 defines the hysteresis).

9.9

Parameters error

Bit 12 of Alarm status (AlSt) indicates that there was a problem during the automatic conversion of the parameters of
temperature and/or pressure and it is possible that not all parameters have been successfully converted.
The automatic conversion of the parameters is performed only at the reset after a change in parameters Ph60 and/or
Ph61.
If this alarm occurs, the user should check and correct all the parameters of temperature and pressure, cancel the
alarm leading to 1 bit 0 of the variable Command (Cmd), and then reset the EVDRIVE03.