Chapter 3: Installation

3-6

2M46-04R/2M46-04RDC User’s Guide

Figure 3-3

Installing the Rackmount Brackets

3.

With the mounting brackets installed, position the 2M46-04R between
the vertical frame members of the 19-inch rack and fasten it securely
with mounting screws as shown in

Figure 3-4

.

Figure 3-4

Installing the 2M46-04R in a Rack

Bonding the Rackmount Brackets to the 2M46-04RDC

If the 2M46-04RDC is going to be mounted in a rack and needs to meet
the GR-1089-CORE Section 9 bonding requirements, use the following
instructions to install the 2M46-04RDC into a 19-inch rack.

1.

Remove and discard the four cover screws (two from each side)
located along the front edges of each side of the 2M46-04RDC.

2.

Remove the paint from around the area near the mounting holes on the
left and right side of the cover of the 2M46-04RDC. See

Figure 3-5

.

3.

Apply a thin layer of anti-oxidant to the surface where the paint was
removed.

Screws (4)

Rackmount Brackets (2)

2314-04

2M46-04R

2

1

HSIM 1

HSIM 2

RESET

COM

PWR

CPU

Screws (4)

19-Inch Rack

HSIM 1

HSIM 2

RESET

COM

2314-03

2M46-04R

2

1

PWR

CPU