beautypg.com

Cte-5100 series thermostat reference, Checkout and calibration – KMC Controls CSP-5002 User Manual

Page 7

background image

CSP-5001/5002 VAV Flow Controller-Actuators

7

Applications Guide, Rev. B

CTE-5100 Series Thermostat Reference

Checkout and Calibration

The thermostat (CTE-5100 series) operates on a 16

volt DC power supply from the CSP controller and

outputs a 0–10 volt DC signal on the T(x) terminals

(Direct Acting T1 and Reverse Acting T2). See the

CTE-5100 Series Thermostat Reference Page for de-

tails on which ‘T’ terminals are used on each model

thermostat, but generally T1 and T3 are used for the

cooling mode and T2 and T4 for heating. T1 and T2

are adjustable to limit minimum and maximum flow.

T3 and T4 have a fixed 0–10 volt DC output signal

(over the proportional band).
NOTE: Limits may be set at the CSP or the CTE

thermostat. If setting the min/max limits

at the CTE thermostat, the CSP’s Min. dial

must be set fully CCW to 0 and the Max.

dial set fully CW to 100. This will ensure

that the CSP will not have any effect on the

limits.

1. Required tools:

• 1/16-inch hex/key wrench
• Small flat blade (1/8-inch) screwdriver
• Digital voltmeter capable of displaying a

0–10 volt DC range which will display in

hundredths of a volt.

• HSO-5001 test leads (optional for meter taps)

2. Remove the thermostat cover by loosening the

setscrews on each side of the thermostat (see

illustration). Using a 1/16-inch hex key wrench,

turn the setscrews clockwise until the cover is

loose.

3. Check voltages:

A. Verify 16 volts DC between (+) and (–)

terminals.

B. Measure “T(x)” to “–” for output voltage. Use

the calibration procedures below to adjust

limits if desired. Adjust the setpoint above and

below current room temperature and observe

changes in appropriate “T” voltage. Remove

setpoint slider stops (HFO-0027) if necessary.

NOTE: Always adjust minimum flow limits first.
4. Maximum limits will always be greater than

minimum limits. (Maximum is additive to

minimum.) If in doubt, turn maximum limit fully

clockwise (increase) before proceeding.

NOTE: Dials rotate approximately 200° (8:00

to 4:00). Turn clockwise to increase or

counterclockwise to decrease. Do not use

excessive force on dials. They should turn

freely and effortlessly. DO NOT force dial

beyond a stop.

5. Connect voltmeter to the meter taps (using the

HSO-5001 test leads adapter makes this easier).
A. Connect to the middle and right terminal (see

illustration) for the minimum and maximum

reading.

B. Connect to the middle and left terminal

for measuring actual flow velocity. (The

thermostat must be wired to a controller for

this option; see the Applications sections).

6. Adjust the minimum flow.

A. Push the cooling setpoint slider all the way to

the right. (This requests minimum flow, and

is normally for heating mode or cooling is

satisfied.)

B. Set the minimum flow voltage as desired

using the Min. dial (on the Cooling side of

thermostat).

7. Adjust the maximum flow.

A. Push the cooling setpoint slider all the way to

the left. (This requests maximum flow, and is

normally for full cooling mode.)

B. Set the maximum flow voltage as desired

using the Max. dial (on the Cooling side of the

thermostat).

8. Adjust the cooling setpoint slider back to its

original position and replace the cover.

NOTE: For use with the CTE-5202 thermostat

instead of the CTE-5100 series, see the

CTE-5202 Applications Guide

.

This manual is related to the following products: