CSP-5001/5002 VAV Flow Controller-Actuators

18

Applications Guide, Rev. B

Cooling with Hot Water Reheat

This application uses a CTE-5104 thermostat with

a VEP-43/VEB-46 series 3-way hot water valve to

control temperature in the conditioned space. The

valve shown below uses the (discontinued) MEP-

5062 or (fail-safe) MEP-5372 actuator for reheat

control.
With 0 VDC from the thermostat, the mixing valve

bypasses water from the supply to the return. As the

thermostat voltage increases, water begins flowing

into the coil to allow heated air into the space. At 2°

below setpoint the full flow is sent through the coil.
NOTE: Jumper “T2” to “R2” for automatic

auxiliary flow for heating.

Valve

Open

(

Colder

Room Temperature

Warmer

)

T2

Signal

Cooling

Max.

Cooling Min.

T1

Signal

Cooling Setpoint

Heating Setpoint

Aux.

Flow

(Former Ref. # APE-1-5017)