CSP-5001/5002 VAV Flow Controller-Actuators

11

Applications Guide, Rev. B

Applications

Cooling or Heating

The CTE-5100 series single-setpoint thermostats are

designed for use with CSP-5000 series electronic VAV

controllers to operate damper boxes and/or valves

in the HVAC system. As shown in the diagram, a

“requested flow” voltage signal (T1 or T2) is wired

to the CSP-5001 to adjust airflow from minimum

to maximum flow according to space demand.

Minimum and maximum flow limit adjustments can

be made at the thermostat or at the controller.

NOTE: CTE-5101 for cooling is shown. For heating,

use CTE-5102, with terminal T2 for input

(“IN”) signal to CSP-5001 controller.

An additional “unrestricted” output (T3 or T4) is

not affected by minimum/maximum limits and

can be used to operate reheat equipment or other

control devices by utilizing REE series relays (some

thermostats vary). See CTE-5100 Series Thermostat

Reference section for details on “T” terminals. The

CTE-5101 has a Direct Acting (DA) reset and the

CTE-5102 employs a Reverse Acting (RA) reset.

CSP–5001

Controller-Actuator

H

~

16

V

DC

I

N

O

U

T

–

–

L

24 VAC

(To Flow Sensor)

24 VAC @ 4 VA

~

–

–

12

V

V1 T3 R1 T1

A

+

CTE–5101 Thermostat

(Optional) Velocity Readout

Jumper

Heating Air

Heating Max.

Heating Min.

1650

fpm

0 fpm

Setpoint

(

Colder

Room Temperature

Warmer

)

3300

fpm

CTE–5102 (T2)

Cooling Max.

Cooling Min.

1650

fpm

0 fpm

Setpoint

(

Colder

Room Temperature

Warmer

)

3300

fpm

T2

Signal

Cooling Air

CTE–5101 (T1)

T1

Signal

NOTE: For use with the CTE-5202 thermostat

instead of the CTE-5100 series, see the

CTE-5202 Applications Guide

.

(Former Ref. # APE-1-5001)