Array index 6 – i/o receive select, Array index 7 – devicenet modules status – Rockwell Automation 2098-IPD-020-DN Ultra5000 Series Intelligent Positioning Drives with DeviceNet Reference Manual User Manual
Page 19

Publication 2098-RM002A-EN-P – October 2001
DeviceNet Driver Installation
2-5
Array Index 6 – I/O Receive Select
Selects the output (consumed) assembly that is updated when a
Polled I/O Message is received by the drive. If the value is modified,
you have to either close any existing I/O Messaging connection(s),
power cycle the drive, reset the drive, or remove and reapply
DeviceNet power for the drive to use the modified value.
Refer to Assembly Object, Instance ID = 1 - 16 on page 4-12 for
information on the data format.
Array Index 7 – DeviceNet Modules Status
This is a read-only value that indicates the last modules fault status.
This value defaults to zero on power up and reset.
Value Description
0
No data consumed
1
2
DNetIntArray[2], DNetIntArray[3]
3
4
DNetFltArray[2], DNetFltArray[3]
5
DNetIntArray[2], DNetFltArray[2]
6
DNetIntArray[2], DNetIntArray[3], DNetFltArray[2]
7
DNetIntArray[2], DNetFltArray[2], DNetFltArray[3]
8
DNetIntArray[2], DNetIntArray[3], DNetFltArray[2], DNetFltArray[3]
Value Description
0
No Fault (default)
1
DeviceNet Idle Fault
2
DeviceNet Comm Fault