Rockwell Automation Publication 1768-UM002C-EN-P - April 2012

Chapter 5

Add, Configure, Monitor, and Replace CIP Safety I/O

Scenario 2 - Replacement Module SNN is Different from Original and Safety Signature Exists

1.

Remove the old I/O module and install the new module.

2.

Right-click your POINT Guard I/O module and choose Properties.

3.

Click the Safety tab.

4.

Click Reset Ownership.

5.

Click OK.

6.

Right-click your controller and choose Properties.

7.

Click

to the right of the safety network number to open the Safety

Network Number dialog box.