Status Indicators

1.

If there is a 1769 power supply installed in the local bank, remove it and
reapply power.

If the I/O PWR indicator remains red, go to the next step.

2.

Remove power and wait for all status indicators to turn off.

3.

Disconnect the 1769 I/O modules from the system.

4.

Reapply power.

5.

Check the controller I/O PWR indicator.
a. If the indicator is red, replace the controller.
b. If the indicator is green, one of the 1769 I/O modules is causing the red

indicator.

To troubleshoot 1769 I/O modules, see their respective installation
instructions.