Status Indicators

Clear a Major Fault

If the OK status indicator flashes red because of a recoverable major fault, clear
the fault by following these steps.

1.

Turn the controller keyswitch from PROG to RUN and back to PROG.

2.

Go online with RSLogix 5000 software.

3.

On the Controller Properties dialog box, click the Major Faults tab to find
information about the fault.

OK

Off

No power is applied. If MEM SAVE indicator is green, the user program and configuration data are being saved to nonvolatile memory.

Flashing Red

The controller requires a firmware update or a firmware update is in progress.
A recoverable major fault occurred on the controller.
A non-recoverable major fault occurred on the controller.
See

Clear a Major Fault on page 118

.

Red

The controller detected a nonrecoverable major fault so it cleared the project from memory.
See

Clear a Nonrecoverable Fault on page 119

.

Green

Controller is OK.

Flashing Green

The controller is storing or loading a project to or from nonvolatile memory.

CF

Off

There is no CompactFlash card activity.

Flashing Green

The controller is reading from or writing to the CompactFlash card.
IMPORTANT: Do not remove the CompactFlash card while the controller is reading from or writing to the card. Removing the card
during a read or write could corrupt data on the card, data in the controller, and firmware installed on the controller.

Flashing Red

The CompactFlash card does not have a valid file system and must be replaced.

DCH0

Off

Channel 0 is configured differently than the default serial configuration.

Green

Channel 0 has the default serial configuration.

CH0

Off

No RS-232 activity.

Green

RS-232 activity.

SAFE RUN

Off

The user safety task or safety outputs are disabled. The controller is in the PROG mode, test mode, or the safety task is faulted.

Green

The user safety task and safety outputs are enabled. The safety task is executing. Safety task signature is present.

Flashing Green

The user safety task and safety outputs are enabled. The safety task is executing. Safety task signature is not present.

SAFETY TASK

Off

No partnership established.

Green

Safety controller status is OK. The coordinated system time (CST) is synchronized and safety I/O connections are established.

Flashing Green

Safety controller status is OK. The coordinated system time (CST) is not synchronized.

Red

Safety partnership was lost.

Flashing Red

Safety task is inoperable.

SAFETY LOCK

Off

Safety task is not locked.

Green

Safety task is locked.

SAFETY OK

Off

No power is applied.

Green

The safety partner is OK.

Flashing Green

The safety partner is storing or loading a project to or from nonvolatile memory.

Red

The safety partner detected a nonrecoverable major fault, so it cleared the project from its memory.

Flashing Red

The internal safety partner requires a firmware update or a firmware update is in progress.
A recoverable major fault occurred on the safety partner.
A nonrecoverable major fault occurred on the safety partner.

Table 35 - Status Indicator Descriptions

Indicator

Status

Description