Store and Load Projects Using Nonvolatile Memory
Chapter 9
Storing a Safety Project
You cannot store a safety project if the safety task status is Safety Task Inoperable.
When you store a safety project, controller firmware is saved to the memory card.
If no application exists in the controller, you can save just the firmware of the
safety controller only if valid partnership exists. A firmware-only load will not
clear a Safety Task Inoperable condition.
If a safety task signature exists when you store a project, the following occurs:
•
Safety tags are stored with the value they had when the signature was first
created.
•
Standard tags are updated.
•
The current safety task signature is saved.
When you store a safety application project on a memory card, we recommend
you select Program (Remote Only) as the Load mode, that is, the mode the
controller should enter following the load.
Loading a Safety Project
You can only initiate a load from nonvolatile memory, if the following is true:
•
The controller type specified by the project stored in nonvolatile memory
matches the controller type.
•
The major and minor revisions of the project in nonvolatile memory
matches the major and minor revisions of the controller.
•
Your controller is not in Run mode.
You have several options for when (under what conditions) to load a project into
the user memory of the controller.
Table 34 - Options for Loading a Project
If you want to load the project
Then select this
Load Image
option
Notes
Whenever you turn on or cycle
power
On Power Up
• During a power cycle, you lose any online changes, tag values, and network schedule that you have not stored in the
nonvolatile memory.
• The controller loads the stored project and firmware at every powerup regardless of the firmware or application on
the controller. The load occurs whether or not the controller is safety-locked or has a safety task signature.
• You can always use RSLogix 5000 software to load the project.
Whenever there is no project in the
controller and you turn on or cycle
power
On Corrupt Memory
• The controller updates the firmware on the controller, if required. The application stored in nonvolatile memory is
also loaded and the controller enters the selected mode, either Program or Run.
• You can always use RSLogix 5000 software to load the project.
Only through RSLogix 5000
software
User Initiated
• If the controller type as well as the major and minor revisions of the project in nonvolatile memory match the
controller type and major and minor revisions of the controller, you can initiate a load, regardless of the Safety Task
status.
• Loading a project to a safety-locked controller is allowed only when the safety task signature of the project stored in
nonvolatile memory matches the project on the controller.
• If the signatures do not match or the controller is safety-locked without a safety task signature, you are prompted to
first unlock the controller.
IMPORTANT: When you unlock the controller and initiate a load from nonvolatile memory, the safety-lock status,
passwords, and safety task signature are set to the values contained in nonvolatile memory once the load is
complete.
• If the firmware on the controller matches the revision in nonvolatile memory, the internal safety partner firmware is
updated, if required, the application stored in nonvolatile memory is loaded so that the Safety Task status becomes
Safety Task Operable and the controller enters the selected mode, either Program or Run.