5.4.9 Flying restart circuit active
If you have activated the flying restart circuit, the assigned output
indicates when the flying restart circuit is active. For further
information about the flying restart circuit see page 95.
5.4.10 Process control active, process step active
If you use the process control, the assigned outputs indicate when
the process control or individual steps are active. For further
information about the process control see page 94.
5.5
Monitor outputs
The inverter has two monitor outputs (terminals 62 and 63), to output
internal signals as voltage or current signals. The required switch
settings can be obtained from the table on page 29.
Factory setting:
Output
Function
Relationship
Terminal 62
Terminal 63
Output frequency
Motor current
10V corresponds to f
dmax
10V corresponds to 200% rated
inverter current
⋅
If you need another signal for an output, first select under C110,
which output you want to change. Under C111 you select the signal
which you want to assign to this output. To adapt the monitor
output, e.g. to a display instrument, you can adjust gain and offset
via C108 and C109.
Code
Parameter
Meaning/Function
Acceptance
C110
-1-
-2-
Monitor output1 terminal 62
Monitor output 2 terminal 63
SH + PRG
C111
-0-
-2-
-5-
-6-
-7-
-9-
-23-
-30-
-31-
No signal
Set-value 1 (10V corresponds to 100%)
Total set-value (total from main set-value and set-
value 2)
PI controller output (10V corresponds to 100%)
PI controller output (10V corresponds to 100%)
Output frequency (10V corresponds to f
dmax
)
Motor current (10V corresponds to 200% of max.
inverter current)
⋅
Motor voltage (10V corresponds to 1000V)
DC bus voltage (10V corresponds to 1000V)
SH + PRG
C108
-10.00...+10.00
Gain
ON-LINE
C109
-1000...+1000mV
Offset
ON-LINE