1 tightening torques of the power terminals, 2 control connections – Lenze 8615E User Manual
Page 29

27
5.1.1 Tightening torques of the power terminals
Type
8601...8605
8606, 8607
8608...8611
8612, 8613
8614, 8615
Tightening
torque
0.6...0.8 Nm
(5.3...7.1 lbfin)
1.2...1.5 Nm
(10.6...13.3 lbfin)
1.5...1.8 Nm
(13.3...16 lbfin)
6...8 Nm
(53...70 lbfin)
15...20 Nm
(133...177 lbfin)
5.2
Control connections
Layout:
X1
X2
X3
X4
X5
X6
X8
X9
V1
V2
E7 E8 39 40 41
44 45
K11 K14 A1
A2 A3 A4 59
60 62 63 VE9 GND FE
1
2
3
4
7
8
9
10 11
12
20
21 22
28
E1 E2 E3 E4 E5 E6
1
5
6
9
5
1
9
6
X11
1
8
9
15
X10
8
1
15
9
1
5
6
9
5
1
9
6
X1 to X4:
Control terminals
X5:
Input of digital frequency/incremental encoder
X6:
LECOM interface (RS232/485)
X8:
2nd input of digital frequency/incremental encoder
(option)
X9:
Output of digital frequency (option)
X10, X11:
Field bus connections
(Option, e.g. 2110IB for InterBus-S)
V1, V2;
Displays for field bus options
Note
Always connect the plug-in terminals (accessory kit) to the plug
connectors X1 to X4.
When not using the interface plugs (plug-in connectors) X5 and X6
protect them with the supplied covers.
It is possible to change the functions of certain control terminals
using switches (see chapters 5.2.1 to 5.2.7, page 28ff ). To adjust
the switches, remove the cover of the device.
In addition to this, there are numerous possibilities to change the
inputs and outputs of the device using codes (see page 78ff).