Lenze 8615E User Manual
Page 20

18
3.3
Application with medium overload,
peak torque up to 135% of the rated motor torque
−
For applications where only small starting and
overload torques are necessary (e.g. ventilators,
pumps).
−
The inverter provides 110% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.1.
−
For this application, the monitoring of the output
current is set to operation with maximum power
using the codes C119 and C120 (see page 97)
−
Please note that a maximum ambient temperature
of 40°C is permissible.
Type
Order no.
Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601
33.8601_E
2.2
5.3
6.0
3.67
4.41
5.3
155
8602
33.8602_E
3.0
7.0
7.8
4.85
5.82
7.0
175
8603
33.8603_E
4.0
9.9
11.0
6.86
8.23
9.2
205
8604
33.8604_E
5.5
12.5
15.0
8.66
10.4
11.6
235
8605
33.8605_E
−
−
−
−
−
−
−
8606
33.8606_E
11.0
22.5
26.0
15.6
18.7
20.5
340
8607
33.8607_E
−
−
−
−
−
−
−
8608
33.8608_E
18.5
42.3
47.0
29.3
35.2
37.2
550
8609
33.8609_E
22.0
57.6
64.0
39.9
47.9
50.0
710
8610
33.8610_E
30.0
62.0
79.0
43.0
51.5
54.0
760
8611
33.8611_E
−
−
−
−
−
−
−
8612
33.8612_E
45.0
95.0
120.0
65.8
79.0
83.0
1110
8613
33.8613_E
55.0
115.0
150.0
79.7
59.6
100.0
1320
8614
33.8614_E
75.0
145.0
178.0
100.5
120.5
125.0
1640
90.0*
160.0*
178.0*
110.9*
133.0
138.0*
1640*
8615
33.8615_E
−
−
−
−
−
−
−
*
These data are valid for a maximum ambient temperature of 30°C.